2005-09-13 00:00:00DENIED;
 1.CLEANOUT REQUIRED ON W/M STACK 4'
 ABOVE FINISH FLOOR.
 2.SHOW CLEANOUT AT JUNCTURE OF BUILDING
 DRAIN AND BUILDING SEWER. SEC 708.3.5.
  
 GAS RISER DIAGRAM; THE FOLLOWING
 INFORMATION IS REQUIRED.
 1. TYPE OF GAS, (LP OR NATURAL)
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). EXISTING GAS
 PIPING, LOAD AND LENGHT MUST BE KNOWN TO
 PROPERY SIZE SYSTEM.
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2 (POINT
 OF USE HEATERS) CHECK CLEARANCE BETWEEN
 HEATER AND LAUNDRY ROOM WINDOW.
 PLUMBING PLAN REVIEW BY;