| Plan Review Notes For Permit 05081926 |
| Permit Number |
05081926 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-13 00:00:00 | DENIED; | | | 1.CLEANOUT REQUIRED ON W/M STACK 4' | | | ABOVE FINISH FLOOR. | | | 2.SHOW CLEANOUT AT JUNCTURE OF BUILDING | | | DRAIN AND BUILDING SEWER. SEC 708.3.5. | | | | | | GAS RISER DIAGRAM; THE FOLLOWING | | | INFORMATION IS REQUIRED. | | | 1. TYPE OF GAS, (LP OR NATURAL) | | | 2. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). EXISTING GAS | | | PIPING, LOAD AND LENGHT MUST BE KNOWN TO | | | PROPERY SIZE SYSTEM. | | | 4. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 (POINT | | | OF USE HEATERS) CHECK CLEARANCE BETWEEN | | | HEATER AND LAUNDRY ROOM WINDOW. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|