Notes
Date Text
2005-09-13 00:00:00*** DENIED ***
 1) CAN NOT HAVE A CASED OPENING BETWEEN
 GARAGE AND AIR CONDITIONED UTILITY ROOM,
 FBC R-309.1 .
 2) RETURN AIR DUCT MUST BE ATTACHED TO
 AHU, NO OPEN AIR PLENUM. OR INSTALL A 20
 MIN. FIRE RATED DOOR TO MECH. ROOM, FBC
 R-309.1
 3) RETURN AIR DUCT NEEDS TO BE 10",
 FBC/M 601.4 .
 4) PLEASE NOTE YOU WILL NEED A GAS
 PERMIT WHEN YOU RUN YOUR GAS LINES.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.