| Notes |
| Date |
Text |
| 2005-09-13 00:00:00 | *** DENIED *** | | | 1) CAN NOT HAVE A CASED OPENING BETWEEN | | | GARAGE AND AIR CONDITIONED UTILITY ROOM, | | | FBC R-309.1 . | | | 2) RETURN AIR DUCT MUST BE ATTACHED TO | | | AHU, NO OPEN AIR PLENUM. OR INSTALL A 20 | | | MIN. FIRE RATED DOOR TO MECH. ROOM, FBC | | | R-309.1 | | | 3) RETURN AIR DUCT NEEDS TO BE 10", | | | FBC/M 601.4 . | | | 4) PLEASE NOTE YOU WILL NEED A GAS | | | PERMIT WHEN YOU RUN YOUR GAS LINES. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|