| Notes |
| Date |
Text |
| 2005-09-10 00:00:00 | ****** UNSAT ****** | | | | | | ** PLEASE SEE PLANS ARE COMING BACK FOR | | | ZONING COMMENTS, PLEASE MAKE THE BELOW | | | MINOR CORRECTIONS AT THIS TIME. | | | | | | | | | 1)NOTE: PLEASE INDICATE NEW FOOTER STEEL | | | AND COLD WATER BOND AT NEW PANEL AT THE | | | DETACHED GARAGE. 250.50,250.32. | | | GRND IS NOTED. | | | | | | 2)NOTE: PLEASE SEE PANEL "A" SCHEDULE | | | OCP SHOWN FOR NEW PANEL "B" SUB PANEL. | | | PLEASE CORRELATE SIZE WITH 240.6 AND | | | 100A SUB PANEL. (APPEARS TO BE A | | | MISPRINT). | | | | | | 3)NOTE: PLEASE SEE 210.8A2, WHICH | | | REQUIRES ALL RECEPT IN GARAGE TO BE | | | GFI/GFI PROTECTED. | | | PLEASE SEE EXISTING AREA WITH NEW BRNACH | | | CIRCUITS FOR UTILITY RM. | | | PLEASE ALSO SEE LAUNDRY RM, GEN PURPOSE | | | RECEPT ALSO WITIN 6' OF L. TUB. | | | | | | 4)NOTE: PLEASEPLANS MENTION EXISTING | | | PANEL TO BE REMOVED, HOWEVER NOTES | | | MENTIONS, PANEL TO REMAIN AS J-BOX. | | | | | | THESE WERE ITEMS REDLINED, HOWEVER PLANS | | | NEED COMMENTS FROM OTHER REVIEWER(S) TO | | | BE ADDRESSED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|