| Plan Review Notes For Permit 05081883 |
| Permit Number |
05081883 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-13 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)PLEASE REVISE THE INSTALLATIN | | | SCHEDULE.NOTE THE FOLLOWING: | | | | | | A.ALL OPENINGS HAVE AN ANCHOR SPACING | | | OF 16", BUT THIS IS NON COMPLIANT FOR | | | SOME OF THE LARGER PANEL SPANS | | | REGARDLESS OF WHICH ANCHORS YOU ARE | | | USING. | | | | | | B.CIRCLE WHICH ANCHOR YOU ARE USING ON | | | THE PRODUCT APPROVAL SO THAT CODE | | | COMPLIANCE CAN BE DETERMINED. | | | | | | C.THE INSTALLATION SCHEDULE STATES | | | THAT YOU ARE USING 24 GAUGE, THE NOA IS | | | FOR 22 GAUGE. |
|