| Plan Review Notes For Permit 05081856 |
| Permit Number |
05081856 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-10-18 00:00:00 | ****CORRECTIONS**** | | | | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | THIRD REVIEW: | | | | | | 1.)PROVIDE ANCHORING INFORMATION TO | | | COMPLY WITH FBC1606.1.3; STRUCTURAL | | | MEMBERS AND SYSTEMS, AND COMPONENTS AND | | | CLADDING IN A BUILDING OR STRUCTURE | | | SHALL BE ANCHORED TO RESIST WIND-INDUCED | | | OVERTURNING, UPLIFT AND SLIDING AND TO | | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | | FORCES TO THE FOUNDATION.WHERE A | | | PORTION OF THE RESISTANCE TO THESE | | | FORCES IS PROVIDED BY DEAD LOAD, THE | | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE | | | USED.SHOW SLAB DETAIL AND METHOD OF | | | SLAB TIE DOWN.FOR EXAMPLE: SLAB | | | THICKNESS, REINFORCEMENT USED, TYPE AND | | | SIZE OF TIE-DOWNS USED.MACHINE BOLTS | | | NOT RECCOMMENDED FOR CONCRETE. | | | | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|