| Plan Review Notes For Permit 05081856 |
| Permit Number |
05081856 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-06 00:00:00 | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | 1.DISTANCES FROM BUILDING STRUCTURE & | | | FRESH AIR INTAKES SUCH AS, WINDOWS, | | | DOORS, VENTS IN ROOF SOFFITS. | | | | | | 2.INFORMATION SUBMITTED INDICATES THIS | | | GENERATOR'S FUEL WILL BE LP GAS.PLEASE | | | PROVIDE LOCATION AND THE CAPACITY OF LP | | | TANK. | | | | | | 3.INDICATE DISTANCES FROM THE PROPERTY | | | LINES & BUILDING STRUCTURE TO THE FUEL | | | TANK. | | | | | | 4.PROVIDE SIZING OF GAS LINE.SHOW | | | COMPLIANCE WITH NFPA 58, SEE THE | | | ATTACHED. | | | | | | ADDTIONAL PERMIT REQUIRED FOR THE LP | | | GAS.CONTRACTOR TO BE A LPG SPECIALTY | | | INSTALLER OR LP GAS DEALER PER FS 527 |
|