| 2005-09-01 00:00:00 | ********** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE MECH COMMENTS AND |
| | SHOW LOCATION DIMENTIONS FROM DWELLING. |
| | PLEASE SEE BLDG REVIEW COMMENTS FOR |
| | SLAB/TIE DOWNOR BOLT DOWN DETAIL |
| | REQUIRED. |
| | |
| | |
| | 2)NOTE: PLEASE SUBMIT TWO COPIES OF |
| | MANUFACTURES SPECS/CUT SHEETS FOR |
| | GENERATOR AND ATS. |
| | PLEASE SEE OWNER MANUAL IS NOT REQUIRED |
| | , JUST THE BASIC CUT SHEETS FOR |
| | GENERATOR AND TRANSFER SWITCH. |
| | |
| | |
| | 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM |
| | FOR ELECTRICAL SERVICE SHOWING |
| | INSTALLATION OF NEW EQUIPMENT. PLEASE |
| | SEE LINE AND LOAD CONDUCTORS CAN NOT BE |
| | LOCATED IN METER CAN. |
| | PLEASE SEE EQUIPMENT GROUNDING |
| | CONDUCTORS ARE ONLY INSTALLED AFTER THE |
| | FIRST MENAS OF DISCONNECT. |
| | 250.6,250.24 ETC |
| | GRND RODS ALSO REQUIRED AT |
| | SERVICE.250.50 |
| | |
| | |
| | 4)NOTE: PLEASE SEE 225.31 FOR MISSING |
| | MEANS OF DISCONNECT. PLEASE SEE 225.34 |
| | FOR GROUPING OF THIS MEANS OF DISCONNECT |
| | WITH EXISTING MAIN. |
| | PLEASE SEE 225.36, THIS DISCONNECTING |
| | MEANS SHALL BE LISED AS "SERVICE |
| | EQUIPMENT". |
| | |
| | 5)NOTE: PLEASE PROVIDE |
| | LOADS/CALCULATIONS FOR ITEMS INSTALLED |
| | ON NEW PANEL. |
| | PLEASE SEE CIRCUITS SHOWN DO NOT SEEM TO |
| | BE ALL CIRCUITS. |
| | PLEASE INDICATE OF ALL APPLIANCES ARE |
| | GAS? ETC |
| | GEN LT AND RECEPTS LOADS ARE THE ONLY |
| | LOADS THAT MAY BE DE-RATED. |
| | ALL APPLIANCE, MOTOR, CONNECTED LOADS |
| | INCLUDING HEAT LOAD FROM A/C SHALL BE |
| | FIGURED AT 100%. |
| | 702.5 |
| | |
| | 6)NOTE: PLEASE INDICATE THE GEN PRIME |
| | MOVER, LP, NAT GAS? |
| | PLEASE SEE CALCS SUBMITTED INDICATE A |
| | 40KA UNIT BEING INSTALLED, WHICH PER |
| | MANUAL WOULD INDICATE THIS AS AN LP |
| | SYSTEM. IS THIS CORRECT? |
| | MANUAL SUBMITTED IS LABLED AS 37KW FOR |
| | NATURAL GAS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |