| 2005-09-02 00:00:00 | ********* UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE 210.52C1 FOR SOME |
| | MISSING GFI RECEPTS ALONG KITCHEN |
| | COUNTERSPACE. |
| | PLEASE ALSO SEE AREA IN KITCHEN AT |
| | MICROWAVE LOCATION APPEARS TO BE |
| | COUNTERSPACE? |
| | PLEASE SEE 210.8A6 FOR ALL RECEPTS |
| | SERVING KITCHEN COUNTERSPACE ARE TO BE |
| | GFI /GFI PROTECTED. |
| | |
| | 2)NOTE: PLEASE SHOW LOCATION OF ALL |
| | SERVICE EQUIPMENT AS SHOWN ON RISER. |
| | PLEASE LABEL PANELS, A, B ETC. |
| | PLEASE SHOW LOCATIONS OF ALL APPLIANCES |
| | AS INDICATED ON PANEL SCHEDULES. |
| | WASHER, DRYER, AHU, CU ETC. |
| | |
| | 3)NOTE: PLEASE SEE 440.11 FOR MISSING |
| | DISCONNECTS FOR A/C EQUIPMENT. |
| | PLEASE SEE 210.63 FOR MISSING GFI FOR |
| | CU. |
| | |
| | 4)NOTE: PLEASE SEE 410.8 FOR MIN |
| | CLEARENCE OF LT FIXTURE IN CLOSET. |
| | |
| | 5)NOTE: PLEASE SEE PLANS INDICATE ARC |
| | FAULT PROTECTION FROM THE PREVIOUS CODE. |
| | PLEASE SEE 2002 NEC 210.12, WHICH |
| | REQUIRES ARC FAULT PROTECTION FOR ALL |
| | OUTLETS IN BEDRMS, LTS, FANS, SD'S |
| | RECEPTS ETC. |
| | |
| | 6)NOTE: PLEASE SEE MISSING RECEPT PER |
| | 210.52 |
| | |
| | 7)NOTE; PLEASE SEE MISSING DEDICATED |
| | BATH CIRCUIT PER 210.52D,210.11C3 MUST |
| | BE 20A #12 |
| | |
| | 8)NOTE: PLEASE PROVIDE PANEL SCHEDULE(S) |
| | SHOWING ALL MINCIRCUITS AND CORRELATE |
| | WITH LOAD CALCULATIONS. |
| | PLEASE SHOW ALL MIN AWG PER NEC 310.16 |
| | PLEASE SEE 3-SMALL APPL CIRCUITS SHOWN |
| | ON PANEL SCHEDULE, ONLY 2 SHOWN IN LOAD |
| | CALCS. |
| | PLEASE SEE CORRELATE ALL ITEMS ON PANEL |
| | SCHEDULE(S) WITH LOADS SHOWN IN LOAD |
| | CALCULATIONS. |
| | (DRYER, A/C SYSTEM,, ETC |
| | |
| | 9)NOTE: PLEASE SEE MIN OCP FOR AHU HEAT, |
| | SHALL BE SIZED PER 424.3B |
| | MIN 125%. |
| | |
| | 10)NOTE: PLEASE SEE 220.16, MIN OF 5KW |
| | SHALL BE FIGURED FOR DRYER. PLEASE SEE |
| | 3.6 SHOWN. |
| | PLEASE ADJUST. |
| | |
| | 11)NOTE: PLEASE VERIFY 2500W WATER |
| | HEATER. PLEASE BE SURE THIS IS THE TOTAL |
| | NAME PLATE RATING AND NOT ONLY ONE |
| | ELEMENT. THISSIZE UNIT SEEMS SMALL FOR |
| | A 1200 SQ FT HOUSE. |
| | |
| | 12)NOTE: PLEASE SEE A/C HEAT LOAD MAY |
| | NOT BE DE-RATED AT 40%. PLEASE SEE |
| | 220.31B FOR LOAD CALCULATIONS. |
| | PLEASE SEE MIN SERVICE SHOWN MENTIONS, |
| | 100A'S, HOWEVER 200A SERVICE IS SHOWN ON |
| | RISER? |
| | |
| | 13)NOTE: PLEASE INDICATE MIN GROUNDING |
| | ELECTRODE SYSTEM PER 250.50. COLD WATER |
| | PIPE AND MIN OF 2-GRNDS RODS. |
| | |
| | 14)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN TO SUB |
| | PANEL. |
| | PLEASE SEE 250.110 AND 250.122 FOR |
| | SIZING. |
| | |
| | 15)NOTE: PLEASE SEE SD'S ARE BEING SHOWN |
| | CONNECTED TO WHAT APPEARS TO BE LAUNDRY |
| | RM LT. IF THIS THE CASE, ARC FAULT |
| | PROTECTION WOULD ALSO BE REQUIRED FOR |
| | THIS CIRCUIT. |
| | |
| | 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 17)NOTE: PLEASE SEE FBC 104.2.1 WHICH |
| | REQUIRES THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR PLANS . |
| | |
| | 18)NOTE: PLEASE SEE 104.6.5, VALUATION |
| | FOR SCOPE OF WORK MUST BE BASED ON FAIR |
| | MARKET VALUE. (CONTRACTORS PRICE) |
| | INCLUDING ALL LABOR AND MATERIALS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |