| Plan Review Notes For Permit 05081654 |
| Permit Number |
05081654 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-16 00:00:00 | *** PROVISO *** | | | 1) PLANS MUST SHOW ANY BUILDING OPENINGS | | | (WINDOWS, DOORS, ROOF & EAVE VENTS). | | | 2) GENERATOR EXHAUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENINGS | | | (WINDOWS, DOORS, ROOF & EAVE VENTS), AND | | | TEN FEET AWAY FROM ADJECENT BUILDING | | | OPENINGS. 2001 FBC/M 804.3.3 . | | | 3) MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS MUST BE SUBMITTED WITH | | | PERMIT APPLICATION. | | | 4) NATURAL GAS PIPING REQUIRES A GAS | | | PERMIT APPLICATION BY A LICENSE PLUMBING | | | CONTRACTOR. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|