| 2005-09-16 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- BRING PLANS BACK TO PALM BEACH COUNTY |
| | TO CORRECT PR NUMBERS. I TALKED TO MRS. |
| | GIL FROM THE COUNTY SHE SAYS THAT THIS |
| | IMPACT FEES RECEIPT (PR#: 05042803) |
| | DOESN'T MATCH THIS PROPERTY. REVISE AS |
| | REQUIRED. BRING BACK CORRECT PAID |
| | RECEIPT AND PLANS STAMPED WITH |
| | CORRESPONDING PR NUMBER. |
| | |
| | 2- NEED RECORDED N.O.C. |
| | |
| | 3- ENERGY CALCS ARE GETTING THE CEILING |
| | FANS CREDIT. REVISE ELECTRICAL PLAN TO |
| | SPECIFY CEILING FAN SIZE IN EACH ROOM |
| | INCLUDING CEILINGS FANS REQUIRED IN THE |
| | GREAT ROOM. SEE TABLE 6-6 CHAPTER 13 FBC |
| | |
| | 4- REVISE ROOF FRAMING PLAN AT ENTRY |
| | PORCH ROOF. CONCRETE BEAM DOESN'T EXTEND |
| | TO THE FOYER AREA. REVISE FRAMING AROUND |
| | KNEEWALL ON THE LEFT HAND SIDE. THERE IS |
| | NOT CONCRETE BEAM. REVISE ROOF FRAMING |
| | PLAN AS REQ'D AND SPECIFY CORRESPONDING |
| | CONNECTORS. SEC. 104.2.1.2 CITY |
| | AMENDEMNTS TO FBC 2001. |
| | |
| | 5- MULLION SIZE SPECIFIED FOR FIXED |
| | WINDOWS AT GREAT ROOM AREA DOESN'T |
| | RESIST THE DESIGN PRESSURES. REVISE AS |
| | REQ'D. SEC. 104.2.1.2 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | 6- TRUSS ANCHOR SCHEDULE: REVISE NUMBER |
| | OF NAILS FOR HUS26. SEE 2005 CATALOGUE. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL FOR: |
| | A) "INSWING" 1HR FIRE RATED DOOR AT |
| | ATRIUM AS SHOWN ON PLANS. |
| | |
| | B) MULLION SIZE SPECIFIED FOR FIXED |
| | WINDOWS AT GREAT ROOM AREA. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |