Plan Review Notes
Plan Review Notes For Permit 05081642
Permit Number 05081642
Review Stop M
Sequence Number 1
Notes
Date Text
2005-09-09 00:00:00*** PROVISO ***
 1) RETURN AIR TRANSFER DUCTS MUST BE
 1 1/2 TIMES THE SUPPLY AIR DUCT.
 7" SUPPLY AIR DUCT = 9" RETURN AIR
 DUCT. 6" SUPPLY AIR DUCT = 8" RETURN
 AIR DUCT. PER 2001 FBC/M 601.4 EX.#1.
  
 2) FLOAT SWITCH DEVICE NEEDED AT
 AUXILIARY DRAIN OUTLET. PER 2001
 FBC/M 307.2.4.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.