| Plan Review Notes For Permit 05081642 |
| Permit Number |
05081642 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-09 00:00:00 | *** PROVISO *** | | | 1) RETURN AIR TRANSFER DUCTS MUST BE | | | 1 1/2 TIMES THE SUPPLY AIR DUCT. | | | 7" SUPPLY AIR DUCT = 9" RETURN AIR | | | DUCT. 6" SUPPLY AIR DUCT = 8" RETURN | | | AIR DUCT. PER 2001 FBC/M 601.4 EX.#1. | | | | | | 2) FLOAT SWITCH DEVICE NEEDED AT | | | AUXILIARY DRAIN OUTLET. PER 2001 | | | FBC/M 307.2.4. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|