| Notes |
| Date |
Text |
| 2005-11-17 00:00:00 | ENTERED PASS FOR JAKE | | 2005-09-08 00:00:00 | PLEASE SEE NOTES ON PLANS FOR GFI AND | | | FIXTURE REQUIREMENTS. | | | | | | PLEASE FIX RISER DIAGRAM PANELS AND | | | SCHEDULES NOTE TWO DIFFENT TYPES. | | | | | | IF YOU ARE GOING TO GROUND ALL | | | DISCONNECTS AND PANELS WITH AN ELECTRODE | | | PLEASE BOND THEM ALL TOGETHER AND MAKE | | | SURE IN DISCONNECTS AND PANELS THAT THE | | | NEUTRALS AND GROUNDS ARE ISOLATED SO AS | | | NOT TO PARALLEL THE GROUNDED CONDUCTOR. | | | | | | JAKE LEAHY644-7291 |
|