Plan Review Notes
Plan Review Notes For Permit 05081447
Permit Number 05081447
Review Stop B
Sequence Number 1
Notes
Date Text
2005-09-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05081447
 ADD: 4200 AUSTRALIAN AV
 CONT:HOLT CONSTRUCTION
 TEL: (954) 755-7200
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING REVIEW
 ACTION:REVIEWED
 PROVISO:
 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 11-4.13.9 DOOR HARDWARE. HANDLES, PULLS,
 LATCHES, LOCKS, AND OTHER OPERATING
 DEVICES ON ACCESSIBLE DOORS SHALL HAVE A
 SHAPE THAT IS EASY TO GRASP WITH ONE
 HAND AND DOES NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING, OR TWISTING OF
 THE WRIST TO OPERATE.LEVER-OPERATED
 MECHANISMS, PUSH-TYPE MECHANISMS, AND
 U-SHAPED HANDLES ARE ACCEPTABLE DESIGNS.
 WHEN SLIDINGDOORS ARE FULLY OPEN,
 OPERATING HARDWARE SHALL BE EXPOSED AND
 USABLE FROM BOTH SIDES.HARDWARE
 REQUIRED FOR ACCESSIBLE DOOR PASSAGE
 SHALL BE MOUNTED NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE FINISH FLOOR.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026