2005-09-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE DATE
 THE SIGNATURE AND SEAL ARE AFFIXED TO
 PLANS SHALL APPEAR ON THE SEAL. FAC
 61G1-16.003, FAC 61G1-16.004(5) AND FS
 481.2055. - TITLE BLOCK MISSING, FAC
 61G1-16.004(2) FIRM LICENSE NUMBER
 (CERTIFICATE OF AUTHORIZATION). FS
 481.219 & 481.2055.
 2. SHEETS PREPAREC BY THE ENGINEERS.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL ALSO LEGIBLY INDICATE
 THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025.
 3. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 FOR THE DRINKING FOUNTAIN. SHOW THE
 FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.4 CONTROLS
 D. 11-4.15.5 CLEARANCES/CLEAR FLOOR
 SPACE.
 E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 5. SHT A5A DETAIL P, FOR THE LAVS SHOW
 SECTION 11-4.19.5 FAUCETS REQUIREMENT.
 6. SHT P1 WATER RISER DIAGRAM. FULL OPEN
 VALVES ARE REQUIRED ON THE TOP OF EVERY
 WATER DOWN FEED PIPE. SECTION 606.1(4).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]