| 2006-09-13 00:00:00 | ***** UNSAT **** |
| | |
| | 1) NOTE: PLEASE REVISE PLANS FOR THE NEW |
| | PROPOSED PORTABLE GENERATOR. RISER STILL |
| | SHOWS A PERMANANT UNIT. PLEASE SEE THE |
| | SPECS SUBMITTED ALSO STILL INDICATE THIS |
| | BEING A PERMANANT INSTALLED UNIT. |
| | IF THIS IS GOING TO BE A "PORTABLE |
| | UNIT", HOW IS THE ATS GOING TO BE AN |
| | ATS? ONCE THIS ATS SENSES THE LOSS OF |
| | POWER THIS WILL TRANSFER OVER TO ?? |
| | PLEASE SHOW HOW THIS NEW SCENERIO WILL |
| | BE CONNECTED AND WIRED INTO THE ATS ETC. |
| | RISER FOR REVIEW OF CODE COMPLIANCE IS |
| | NOT COMPLETE OR REVISED AT THIS TIME. |
| | |
| | FBC 106.1.2, ADMIN SECT. |
| | 2002 NEC |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |