Plan Review Notes
Plan Review Notes For Permit 05081409
Permit Number 05081409
Review Stop E
Sequence Number 7
Notes
Date Text
2006-09-13 00:00:00***** UNSAT ****
  
 1) NOTE: PLEASE REVISE PLANS FOR THE NEW
 PROPOSED PORTABLE GENERATOR. RISER STILL
 SHOWS A PERMANANT UNIT. PLEASE SEE THE
 SPECS SUBMITTED ALSO STILL INDICATE THIS
 BEING A PERMANANT INSTALLED UNIT.
 IF THIS IS GOING TO BE A "PORTABLE
 UNIT", HOW IS THE ATS GOING TO BE AN
 ATS? ONCE THIS ATS SENSES THE LOSS OF
 POWER THIS WILL TRANSFER OVER TO ??
 PLEASE SHOW HOW THIS NEW SCENERIO WILL
 BE CONNECTED AND WIRED INTO THE ATS ETC.
 RISER FOR REVIEW OF CODE COMPLIANCE IS
 NOT COMPLETE OR REVISED AT THIS TIME.
  
 FBC 106.1.2, ADMIN SECT.
 2002 NEC
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  