2006-06-25 00:00:00****** UNSAT *******
  
 1) NOTE: PLEASE SEE PANEL STP IS SHOWING
 WRONG CONDUCTOR SIZES. THE OCP AND AWG
 WAS REDLINED ON THREE SETS OF PREVIOUS
 PLANS AND MUST BE CORRECTED.
 PLEASE ALSO SEE CU LOAD IS SHOWN AS
 10.4KW, YET THE OCP IS ONLY 30A'S??
 PLEASE REVISE AND ADJUST.
 240.4,310.16, 424.3B, ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  