Plan Review Notes
Plan Review Notes For Permit 05081409
Permit Number 05081409
Review Stop E
Sequence Number 3
Notes
Date Text
2005-12-19 00:00:00********** UNSAT **********
  
  
 1)NOTE: PLEASE SEE 424.3B WHICH REQUIRES
 THE MIN OCP FOR AHU TO BE 125%, (60A)
 FOR A 10KW UNIT.
  
 2)NOTE: PLEASE SEE INCREASE IN GENERATOR
 TO 25KW WITH 125A OCP AT GENERATOR,
 HOWEVER FEEDERS ARE ONLY RATED AT 100A'S
 AND SHOWS 125A OCP.
 PLEASE ADJUST.
 PLEASE SEE EITHER 310.15B6 OR 310.16 FOR
 SIZING.
  
 3)NOTE: PLEASE PROVIDE THE MANUFACTURES
 CUT SHEET WHICH INDICATES THE KW RATING
 FOR THIS UNIT @ NG AND LP.
 NOTE: 25KW IS TYPICALLY THE RATING ON
 LP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  