| Plan Review Notes For Permit 05081409 |
| Permit Number |
05081409 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-12-19 00:00:00 | ********** UNSAT ********** | | | | | | | | | 1)NOTE: PLEASE SEE 424.3B WHICH REQUIRES | | | THE MIN OCP FOR AHU TO BE 125%, (60A) | | | FOR A 10KW UNIT. | | | | | | 2)NOTE: PLEASE SEE INCREASE IN GENERATOR | | | TO 25KW WITH 125A OCP AT GENERATOR, | | | HOWEVER FEEDERS ARE ONLY RATED AT 100A'S | | | AND SHOWS 125A OCP. | | | PLEASE ADJUST. | | | PLEASE SEE EITHER 310.15B6 OR 310.16 FOR | | | SIZING. | | | | | | 3)NOTE: PLEASE PROVIDE THE MANUFACTURES | | | CUT SHEET WHICH INDICATES THE KW RATING | | | FOR THIS UNIT @ NG AND LP. | | | NOTE: 25KW IS TYPICALLY THE RATING ON | | | LP. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|