2005-09-09 00:00:00****UNSAT ****
  
 1)NOTE: PLEASE SEE SPECS/MANUFACTURE
 SHEETS SUBMITTED CONTAIN TWO DIFFERENT
 ATS SWITCHES, PANELS.
 PLEASE SEE 225.31 WHICH REQUIRES A MEANS
 OF DISCONNECT ON THE LOAD SIDE OF
 TRANSFER SWITCH.
 IT IS NOTEDTHAT PANEL SHOWN ON RISER
 INDICATES A MCB, HOWEVER SPECS SUBMITTED
 DOES NOT CORRELATE WITH THIS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  