| Plan Review Notes For Permit 05081390 |
| Permit Number |
05081390 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-15 00:00:00 | WHERE DOES THE FEED COME FOR PANEL "B" | | | IT IS NOT SHOWN ON PANEL "A" SCHEDULE. | | | | | | GROUND ROD TO SMALL FOR PANEL "B" | | | 250.66, 250.53E | | | | | | GROUNDING ELECTRODES SHALL BE COMMON | | | ELECTRODES TO BE BONDED TO EACH OTHER. | | | | | | NEUTRAL SHALL NOT BE BONDED AT PANEL "B" | | | 250.24A5 |
|