2006-03-15 00:00:00WHERE DOES THE FEED COME FOR PANEL "B"
 IT IS NOT SHOWN ON PANEL "A" SCHEDULE.
  
 GROUND ROD TO SMALL FOR PANEL "B"
 250.66, 250.53E
  
 GROUNDING ELECTRODES SHALL BE COMMON
 ELECTRODES TO BE BONDED TO EACH OTHER.
  
 NEUTRAL SHALL NOT BE BONDED AT PANEL "B"