2005-09-04 00:00:00******** UNSAT ***********
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 SUBMITTED STATED INSTALLATION OF A NEW
 70KW HOME GENERATOR, HOWEVER SPECS ETC
 SUBMITTED INDICATE 80KW?
 PLEASE CORRELATE.
  
 2)NOTE: PLEASE SEE OVERVIEW OF
 EQUIPMENT, GEN ETC SHOWN ON SLAB DETAIL
 PAGE DOES NOT INCLUDE LOCATION OF NEW
 ATS.
 PLEASE SEE 230.70, A MAIN DISCWITH
 OVERCURRENT PROTECTION OUTSIDE ON THE
 LINE SIDE OF NEW ATS WILL BE REQUIRED AS
 NO MORE THAN 8' OF UNPROTECTED
 CONDUCTORS IS PERMITTED INSIDE DWELLING.
  
 3)NOTE: PLEASE SEE ATS IS REQUIRED TO BE
 RATED AS SERVICE EQUIPMENT. THIS
 NOTATION COULD NOT BE LOCATED ON SPECS
 SUBMITTED.
 225.36, 230.66
  
 4)NOTE: PLEASE SEE THE DISCONNECTING
 MEANS FROM GENERATOR SHALL BE GROUPED OR
 IMMEDIATELY ADJACENT/CLOSE PROXIMITY.
 225.34
  
 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 PERTAINING TO SURVEY SUBMITTED.
 PLEASE SEE FAC 61G17-7.002, FS 472.025
 WHICH REQUIRES THE SURVEYOR TO SIGN
 SURVEY'S WITH AN ORIGINAL SIGNATURE.
 PLEASE SEE SURVEY SUBMITTED CONTAINS A
 RAISED SEAL OVER A PHOTOCOPIED
 SIGNATURE.PLEASE CALL FOR OPTIONS OF
 SURVEY.
  
 7)NOTE: PLEASE SEE VALUATION SHALL
 INCLUDE GENERATOR, TRANSFER SW (NEMA-1
 OR 3?) AND ALL LABOR AND MATERIALS.
 FBC 104.6.5ADMINISTRATIVE AMENDMENTS.
 PLEASE ADJUST.
  
 8)NOTE: PLEASE SEE AN "EQUIPMENT
 GROUDING CONDUCTOR IS BEING SHOWN FROM
 METER TO THE LINE SIDE OF ATS SHOWN.
 PLEASE SEE 250.6, 250.24 "EQUIPMENT
 GROUNDING CONDUCTORS' ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW