| Plan Review Notes For Permit 05081350 |
| Permit Number |
05081350 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-05-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEWS: | | | | | | 1. SHTS P2.1.1, P2.1, P3.1.1, & P3.1, | | | UNDERGROUND DRAINAGE PIPING PARALLEL | | | WITH THE FOOTER SHALL COMPLY WITH | | | SECTION 307.4. BUILDING DRAIN SHOULD BE | | | MOVED AWAY FROM THE FOOTERS. "OUT OF THE | | | MONOLITHIC FOOTER". (MINIMUM 4' FROM | | | BLOCK WALL). | | | | | | **************NEW COMMENTS************** | | | 1B. SHTS P2.2, P2.3, P2.3.2, P3.2, | | | P3.2.4, P3.3, P3.3.1, P3.3.2, & P4.1 THE | | | INFORMATION REQUIRED ON THE SEAL IS NOT | | | BEING IMPRESSED ON THE SHEET AS REQUIRED | | | IN FAC 61G15-23.002 & FS 471.025.- | | | THE ENGINEER SHALL SIGN HIS/HER NAME. | | | THE INITIALS ARE NOT ACCEPTABLE AND DO | | | NOT APPEAR TO MATCH THE SIGNATURE ON THE | | | OTHER SHEETS. FAC 61G15-23.002(1) & FS | | | 471.025.(ONE SET OF PLUMBING SHEETS | | | WILL BE WITH-HELD FOR POSSIBLE REVIEW BY | | | DBPR).-NEW SEAL WITH "LICENCE" | | | REQUIRED ON ALL SHEETS SEALED AFTER DEC. | | | 31, 2005 PER THE LETTER FROM THE FLORIDA | | | BOARD OF PROFESSIONAL ENGINEERS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|