| 2006-06-06 00:00:00 | PROVISO:2001 FBC/BUILDING 6/6 UNITS |
| | |
| | PLEASE REVISE PLANS TO REFLECT THE |
| | IMPLEMENTATION OF THE PROVISO'S. |
| | |
| | 1.THE FIRST FLOOR MECHANICAL PLAN (M1) |
| | DOES NOT MATCH THE FIRST FLOOR |
| | ARCHITECTURAL PLAN (A-2.0.1).PLEASE |
| | NOTE, RETURN AIR BETWEEN THE GARAGE DOOR |
| | & THE FOYER DOOR IS NOT REQURIED PER |
| | 2001 FMC 601.4 EXCEPTION #3, R/A IS ONLY |
| | REQUIRED FROM HABITABLE SPACES. |
| | |
| | 2.PLAN SHEET M0.1 THE AHU MOUNTING |
| | DETAIL NOTE 15 STATES, "NO COMBUSTIBLES |
| | ALLOWED IN THE MECHANICAL CLOSET" AS |
| | THIS SERVES AS A RETURN AIR PLENUM.THE |
| | DOOR SCHEDULE ON PLAN SHEET A-4.1.1 |
| | INDICATES THE AHU CLOSET DOOR AS A WOOD |
| | LOUVERED DOOR.PLEASE VERIFY WITH THE |
| | DOOR MANUFACTURE THAT THIS WILL MEET THE |
| | REQUIRED 25 FLAME/50 SMOKE INDEX AS |
| | SPECIFIED IN 2001 FMC 602.2.1. |
| | |
| | 3.OUTSIDE AIR CALCULATIONS INDICATED |
| | ON PLAN SEET M0.1 ARE BASED ON |
| | INFLITRATION RATES.THE INFILTRATION |
| | RATES ARE THE "MAXIMUM" ALLOWED BY CODE |
| | & MAY NOT BE A "TRUE/ACTUAL" RATE. |
| | PLEASE PROVIDE CALCS IN ACCORDANCE WITH |
| | 2001 FMC 402.2, 402.2.1 OR TABLE 403.3. |
| | PLEASE NOTE, 6" O.A. DUCT IS INDICATED |
| | ON M2.PLEASE REMOVE FROM THE PLAN IF |
| | THIS DUCT WILL NOT BE INSTALLED. |
| | |
| | 4.SPECIFIC DRYERS ARE TO BE INSTALLED |
| | BY FINAL INSPECTION. |
| | |