| 2006-05-14 00:00:00 | REDLINED PLANS. | | | | | | OCP FOR AHU, MIN 125%, SHOWS 40A OCP. | | | 424.3B. | | | | | | MIN SIZE GEC TO BE 2/0 PER SEC'S PER | | | 250.66 | | | | | | ** | | | PLEASE ONLY REVISE WHEN AND IF OTHER | | | REVISIONS ARE MADE , AFTER PERMIT IS | | | ISSUED. |
|