| Plan Review Notes For Permit 05081350 |
| Permit Number |
05081350 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-02-14 00:00:00 | DENIED:BUILDING #6 / 6 UNITS | | | PLEASE REFERENCE COMMENTS FROM REVIEW | | | DATED 9-28-05, SINCE A RESPONSE SHEET | | | WAS NOT SUBMITTED & FOR CONSISTENCY THE | | | SAME NUMBER SEQUENCE WILL BE USED. | | | | | | 1.COMMENT ADDRESSED | | | | | | 2.PLAN SHEET A-0.0.0, PROJECT | | | INFORMATION; PLEASE INDICATE WHAT TYPE | | | OF SPRINLERED SYSTEM WILL BE INSTALLED | | | I.E. 13, 13D, 13R? | | | | | | 3.COMMENT ADDRESSED. | | | | | | 4.PLAN SHEET A-10.2.0 INDICATES FIRE | | | RATED ASSEMBLIES.DETAIL #5 SHOWS A 1 | | | HR FIRE RATED FLOOR/CEILING ASSEMBLY. | | | PLEASE INDICATE WHAT EDITION OF THE UL | | | BOOK THIS ASSEMBLY WAS TAKEN FROM? THE | | | DETAIL #6 FOR THE DUCT PENETRATION DOES | | | NOT ADDRESS THE MEMBRANE PENETRATION | | | WHERE THE DUCT & GRILLES ARE LOCATED | | | BETWEEN THE RATING OF THE FLOOR/CEILING | | | ASSEMBLY.PLEASE CLARIFY.PLESE NOTE | | | DETAIL #1 & 2 ARE PENETRATIONS THROUGH | | | CONCRETE FLOOR OR WALL ASSEMBLY. PLEASE | | | PROVIDE DETAIL FOR THE WOOD FLOOR | | | SYSTEM. | | | | | | 5 THROUGH 10COMMENTS ADDRESSED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|