| Date |
Text |
| 2006-01-20 00:00:00 | ************** UNSAT 2ND REVIEW ******** |
| | |
| | **PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE ALSO SEE SOME NEW NOTES DUE TO |
| | CHANGES IN PLANS. |
| | |
| | |
| | SUB 1)NOTE: PLEASE SEE PREVIOUS NOTE |
| | WITH RESPECT TO THE 2003 NFPA-101 BEING |
| | ADOPTED AS OF JAN 1ST,2005, HOWEVER |
| | PLANS ARE STILL SHOWING 2002 EDITION. |
| | PLEASE SEE ALL PLANS, A-SHEETS AND |
| | ELECTRICAL SHEETS SHOULD REFERENCE |
| | CURRENT CODES IN EFFECT. |
| | PLEASE LIST THE 2002 NFPA-72, 2003 |
| | NFPA-101, AND THE 2002 NFPA-72. |
| | PLEASE ALSO SEE A-0.00 |
| | |
| | |
| | |
| | |
| | 1)NOTE: NOTE #1 OK, HOWEVER SEE NEW |
| | NOTES DUE TO NEW SERVICE FOR BLDG BEING |
| | SHOWN. SEE NEW NOTES LISTED SEPARATELY |
| | BELOW. |
| | |
| | |
| | 2)NOTE: NOTE #2 NO: |
| | ** PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | AIC RATINGS ARE SHOWN FOR EACH PANEL, |
| | BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW |
| | SERVICE). |
| | PLEASE SEE CALCUALTIONS SUBMITTED ARE |
| | BASED ON UNIT MAINS, WHICH ARE OK, |
| | HOWEVER PLEASE SEE THE MAIN IS ALSO |
| | REQUIRED. THE SEC'S ARE NOT 2/0'S. |
| | |
| | |
| | 3)NOTE: NOTE #3 OK, RECEPT RELOCATED. |
| | |
| | 4))NOTE: NOTE #4 OK, CORRECTED. |
| | |
| | 5)NOTE: NOTE #5 OK. |
| | |
| | 6)NOTE: NOTE #6 OK. |
| | |
| | 7)NOTE: NOTE #7 NO, ??PLEASE SEE THIS |
| | COULD NOT BE LOCATED ON LOAD CALCS. |
| | PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS NEEDS |
| | TO BE SHOWN ABOVE THE GEN. KT/RECEPT |
| | LOADS. THIS SHOULD BE ABOVE THE FIGURED |
| | 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 8)NOTE: NOTE #8 NO, PLEASE SEE AN EFFORT |
| | WAS MADE TO LIST THESE, HOWEVER PLEASE |
| | SEE LISTING INDICATES "GFI" WHEREAS |
| | "AFCI" PROTECTION IS REQUIRED. |
| | |
| | ** PLEASE LIST ALL THE REQUIRD ARC |
| | FAULT PROECTED CIRCUITS AS REQUIRED PER |
| | 2002 210.12 |
| | PLEASE KNOW, SD'S ARE BEING SHOWN |
| | CIRCUITED TO KITCHEN LIGHTING CIRCUIT, |
| | THIS IS OK, HOWEVER PLEASE KNOW, THIS |
| | WOULD ALSO REQUIRE ARC FAULT PROTECTION |
| | FOR THIS ADDITIONAL CIRCUIT. |
| | THIS IS ONLY A NOTE: |
| | |
| | 9)NOTE: NOTE #9 OK, NOTE WAS ADDED TO |
| | PLANS, HOWEVER PLEASE SEE SD'S ARE STILL |
| | BEING SHOWN WITHIN 20' OF COOKING |
| | APPLIANCES. THIS IS PERMITTED, HOWEVER |
| | PLEASE SPECIFY THE SD TO BE INSTALLED IN |
| | ORDER TO MEET EXCEPTION AS LISTED. |
| | |
| | **PLEEASE SEE NFPA-72 (2002) |
| | EDITION,11.8.3.5. |
| | PLEASE PLACE NOTE ON PLANS WHICH STATES |
| | LOCATIONS OF SD'S TO BE A MIN OF 3' FROM |
| | BATH(S) AND KITCHEN DOORS AND 20' FROM |
| | KITCHEN COOKING APPLIANCES. |
| | ** PLEASE SEE EXCEPTION TO 20' FROM |
| | COOKING WITH TYPE OF SD USED.** |
| | PLEASE SEE PLANS SHOWS A SD IN KITCHEN |
| | AREA AT THIS TIME. |
| | |
| | 10)NOTE: NOTE #10 OK, REMOVED. |
| | |
| | 11)NOTE: NOTE #11 NO. |
| | THIS IS REQUIRED ON ALL SHEETS. |
| | |
| | **PLEASE SEE ARCHITECTS TITLE |
| | BLOCK SHALL ALSO CONTAIN THE PRINTED |
| | LICENSE NUMBER FOR ARCHITECT OF RECORD. |
| | FAC 61G1-16.004. |
| | PLEASE SEE THIS COMMENT IS FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | PLEASE KNOW THIS COMMENT DOES NOT APPLY |
| | TO KAMM CONSULTING'S TITLE BLOCK. |
| | |
| | ********** NEW NOTES ************* |
| | |
| | 1)NOTE: PLEASE SEE 250.66 FOR MIN |
| | GROUNDING ELECTRODE CONDUCTOR REQUIRED. |
| | #4 AWG SHOWN, MIN 3/0 AWG. |
| | |
| | 2)NOTE: PLEASE SEE CONDUITS FROM FPL IS |
| | SHOWING AN "EQUIPMENT GROUNDING |
| | CONDUCTOR" TO THE METER CENTER. PLEASE |
| | SEE 250.6,250.24. |
| | AN "EQUIPMENT GROUNDING CONDUCTOR" IS |
| | ONLY INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | PLEASE REMOVE. |
| | |
| | 3)NOTE: PLEASE INDICATE THE OCP AT THE |
| | METER CENTER FOR ALL UNIT BRKRS.215.5 |
| | |
| | 4)NOTE: PLEASE SHOW SERVICE ON PLANS. |
| | PLEASE SEE ELECTRICAL PLANS DO NOT |
| | INDICATE THE LOCATION OF SERVICE ON |
| | EITHER END OF BLDG. PLEASE ALSO NEEDS TO |
| | BE SHOWN ON THE A-SHEETS, FLR PLANS, |
| | ELEVATION. |
| | |
| | 5)NOTE: PLEASE SEE PLANS SHALL CONTAIN |
| | THE SIGNATURE OF THE ENGINEER OF RECORD. |
| | PLEASE SEE NEW SHEETS CONTAIN "INITIALS" |
| | ONLY AND DO NOT CORRELATE WITH THE |
| | ORIGINAL PLANS. |
| | FS 471.025, FAC 61G15-23.002 |
| | PLEASE SEE THIS IS REQUIRED FOR ALL |
| | SHEETS AND FOR ALL TRADES. PLEASE SEE |
| | PLUMB SHEETS WHICH ARE ALSO INITIALED. |
| | PLEASE SEE "RAISED SEAL" SHALL BE CLEAR |
| | AND VISABLE WITH ALL INFORMATION ON |
| | SIADE SEAL. PLEASE SEESHEETS, |
| | INFORMATION ON SEAL IS NOT VISABLE EVEN |
| | WHEN "SHADOWED WITH PENCIL". |
| | |
| | PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |