| 2006-02-28 00:00:00 | DENIED |
| | |
| | 1) THE 2001 FBC DOES NOT ALLOW HEIGHT OR |
| | AREA INCREASES FOR NFPA 13R SPRINKLER |
| | SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D). |
| | FBC 903.2 REQUIRES A NFPA 13 SPRINKLER |
| | SYSTEM. |
| | |
| | 2) THE DOOR TO THE EXIT STAIRS AT THE |
| | SECOND FLOOR MUST PROVIDE A 32" CLEAR |
| | OPENING FROM THE FACE OF THE DOOR TO THE |
| | STOP WITH THE DOOR OPEN 90 DEGREES. SEE |
| | FBC 1003.2.1 AND 1003.2.2. THE 2-8 DOOR |
| | SPECIFIED DOES NOT COMPLY. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC MECH. TABLE |
| | 403.3 FOR THE REQUIRED OUTDOOR AIR |
| | VENTILATION AT GARAGES OF 100 CFM PER |
| | CAR. |
| | |
| | 4) SEE MECHANICAL COMMENTS FOR DUCT |
| | PENETRATIONS THROUGH FIRE RATED |
| | ASSEMBLIES. |
| | |
| | 5) THE TRUSS LAYOUT AND DRAWINGS ARE ARE |
| | REQUIRED TO BE REVIEWED AND APPROVED BY |
| | THE DESIGNER OF RECORD FOR THE |
| | STRUCTURE. IF ACCEPTABLE, THE STRUCTURAL |
| | ENGINEER SHOULD STAMP AND SIGN THE TRUSS |
| | LAYOUT AS SUCH. |
| | |
| | 6) THE TRUSS DRAWING INDEX SHEET IS |
| | INCOMPLETE. SEE FAC 61G15-31.003. THE |
| | NAME OF THE AUTHORITY HAVING |
| | JURISDICTION, THE LOADS AND NAME & DATE |
| | OF THE APPLICABLE BUILDING CODE IS |
| | REQUIRED. |
| | |
| | 7) THE UPLIFT PRESSURES IN THE TRUSS |
| | ANCHOR SCHEDULE ARE INCORRECT FOR THE |
| | SIMPSONHETAL 12 AND THE USP USC. THE |
| | CORRECT UPLIFTS ARE 1265# FOR THE HETAL |
| | 12 AND 11,150 FOR THE USC WITH 4 BOLTS |
| | PER 2005 CATALOGS. THESE ARE THE VALUES |
| | THAT DO NOT INCLUDE A STRESS INCREASE |
| | FOR THE STEEL CALULATIONS. |
| | |
| | 8) THE STATE PRODUCT APPROVALS SUBMITTED |
| | FOR THE TRUSS CONNECTORS DO NOT LIST ALL |
| | THE CONNECTORS THAT ARE LISTED IN THE |
| | TRUSS ANCHORS SCHEDULE. |
| | |
| | 9) SUBMIT STATE PRODUCT APPROVALS FOR |
| | THE 3/4 HOUR FIRE RATED 6 PANEL DOOR AT |
| | THE ENTRY. DOOR #1 IN THE SCHEDULE. |
| | |
| | 10) THE MIAMI-DADE NOA FOR THE SINGLE |
| | HUNG WINDOWS HAS THE INSTALLATION |
| | DRAWINGS FOR THE FIXED GLASS WINDOWS |
| | ATTACHED. PLEASE REMOVE AND ATTACH THE |
| | CORRECT DRAWINGS. |
| | |
| | 11) THE DECORATIVE SHUTTERS ARE REQUIRED |
| | TO BE APPLIED FOR UNDER A SEPARATE |
| | PERMIT. |
| | |
| | 12)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |