| Date |
Text |
| 2005-11-19 00:00:00 | DENIED; |
| | 1.GUTTERS AND DOWN SPOUTS; SHOW |
| | CALCULATIONS AND SIZES PER FBC PLUMBING |
| | CHAPTER 11. |
| | 2.U/G DRAINAGE PIPE PARALLEL TO THE |
| | FOOTER MUST COMPLY WITH SECTION 307.4. |
| | BUILDING DRAIN SHOULD BE MOVED AWAY FROM |
| | FOOTERS. |
| | 3.WATER HEATER RELIEF VALVE DISCHARGE. |
| | SHT P0.1 (WATER HEATER DETAIOL) SHOWS |
| | DISCHARGE TO GARAGE FLOOR. PAGE P2.1 |
| | (FLAT DRAWING) SHOWS P & T DISCHARGE TO |
| | OUTSIDE. REFURE TO SEC.504.7.1. REVISE |
| | PLANS. |
| | 4.BACKFLOW PROTECTION FOR EACH BUILDING |
| | IS REQUIRED. PLEASE ADD NOTE TO |
| | DRAWINGS. |
| | 5.SHOW HOW THERMAL EXPANTION WILL BE |
| | CONTROLLED. SEC. 607.3 THRU 606.3.2. |
| | 6.SHOW SHUTOFF VALVE FOR WATER HEATER ON |
| | RISER DIAGRAMS. |
| | 7.SHOCK ARRESTORS TO BE INSTALLED PER. |
| | MANUFACTURES INSTALLATION INSTUCTIONS, |
| | AS CLOSE TO THE SOURCE OF HAMMER IN A |
| | DIRECT LINE. |
| | 8.WATER RISER DIAGRAMS (FIRST FLOOR) |
| | CHANGE 1/2" HOT TO 3/4" HOT. SECOND |
| | FLOOR WATER RISERS SHOW 3/4" UP FROM |
| | FIRST FLOOR. |
| | 9.SHOCK ARRESTORS ARE REQUIRED ON W/M'S |
| | SEC. 604.9. SHOW ON WATER RISER |
| | DIAGRAMS. |
| | 10.SHOW CLEANOUT ON WASHER STACK AT 48" |
| | A.F.F. SO W/M DOES NOT HAVE TO BE MOVED |
| | IF CLEANING IS REQUIRED. |
| | 11.ALL THIRD FLOOR SAN. RISER DIAGRAMS; |
| | OFFSET VENT THRU ROOF AND ADD A NOTE. NO |
| | PENATRATIONS THRU FIRE RESISTANT |
| | PLYWOOD. SEE PAGE S-2 NOTE 2. |
| | 12.PAGE P3.2.4 FLAT DRAWING UNIT B |
| | OPTION 5 REVERSE, W/M VENTNOT PER RISER |
| | DIAGRAM (MARKED IN RED ON ON SET OF |
| | PLANS) |
| | PLUMBING PLAN REVIEW BY |
| | JOHN LEECH |
| | 805-6695 |