| 2005-09-28 00:00:00 | DENIED: |
| | 1.THE ENERGY CALCULATIONS INDICATE |
| | 'SINGLE FAMILY' & PLAN SHEET A-0.0.0, |
| | INDICATES OCCUPANCY CLASSIFICATION AS |
| | GROUP R2, MULTI-FAMILY.ENERGY |
| | CALUCALTIONS SHOULD REFLECT |
| | MULTI-FAMILY. |
| | |
| | 2.PLAN SHEET A-0.0.0, PROJECT |
| | INFORMATION; TABLE 500 THE TYPE OF |
| | CONSTRUCTION IS LISTED AS TYPE VI, |
| | UNPROTECTED, SPRINKLERED.PER 2001 FBC |
| | TABLE 500 NOTE D; HEIGHT INCREASES NOT |
| | PERMITTED IN APPLICATIONS UTILIZING NFPA |
| | 13R SYSTEMS. |
| | |
| | 3.PLAN SHEETS A-4.0.2 THROUGH A-4.5.3 |
| | NOTE #25 1-HOUR RATED CHASE REFER TO |
| | DETAIL 11/A-13 (AT LIVE WORK OPTION |
| | ONLY).PLEASE CLARIFY IF THE INTENT IS |
| | FOR FUTURE 'LIVE WORK' UNITS. |
| | |
| | 4.PLAN SHEET A-10.2.0 INDICATES FIRE |
| | RATED ASSEMBLIES.DETAIL #5 SHOWS A 1 |
| | HOUR FIRE RATED FLOOR/CEILING ASSEMBLY. |
| | PLEASE PROVIDE A DETAIL FOR THE DUCT |
| | PENETRATIONS.PLEASE NOTE, PER 2001 |
| | FBC(M)607.4 DUCTS EXTENDING THROUGH MORE |
| | THAN ONE FLOOR SHALL BE PROTECTED BY A |
| | SHAFT ENCLOSURRE.PROVIDE UL DESIGN # |
| | FOR DUCT PENETRATIONS. |
| | |
| | 5.PLAN SHEET M1, CONDENSING UNIT SLAB |
| | SHALL BE A MINIMUM OF 3 1/2" AND EXTEND |
| | A MINIMUM OF 2" ABOVE THE ADJOINING |
| | GRADE. |
| | |
| | 6.PLAN SHEET M3 UNIT A OPT.7, TRANSFER |
| | GRILLE FROM THE MASTER SUITE IS NOT |
| | SIZED PROPERLY.PER 2001 FBC(M)601.4 |
| | EXCEPTION #2 & 3, TO ACHIEVE PROPER AIR |
| | BALANCE TRANSFER GRILLES SHALL USE 50 SQ |
| | INCHES OF GRILLE AREA TO 100 CFM OF |
| | SUPPLY AIR.ALL AIR INTO THE MASTER |
| | SUITE IS TO BE INCLUDED.PLAN INDICATES |
| | 375 CFM INTO THE MASTER SUITE THEREFOR |
| | THE TRANSFER GRILLE SHALL HAVE A MINIMUM |
| | OF 187.5 SQ INCHES OF GRILLE AREA.DOOR |
| | SHALL HAVE A 1" UNDERCUT.PLEASE REVISE |
| | PLANS ACCORDINGLY. |
| | |
| | 7.PLEASE PROVIDE OUTSIDE AIR |
| | CALUCLATIONS IN ACCORDANCE WITH 2001 |
| | FBC(M) 402.2, 402.2.1 OR TABLE 403.3. |
| | |
| | 8.PLEASE PROVIDE DETAIL FOR THE |
| | HANGING OF THE AHU LOCATED AT THE 2ND |
| | FLOOR CEILING. |
| | |
| | 9. AUXILIARY DRAIN PAN WITH OVERFLOW |
| | PROTECTION REQUIRED PER 2001 FBC(M) |
| | 307.2.3. |
| | |
| | 10. ELECTRICAL PLANS INDICATE A 'DRYER |
| | BOOSTER FAN'.THIS WILL HAVE TO BE |
| | SUBMITTED TO THE BUILDING OFFICIAL AS |
| | ALTERNATE MATERIALS AND METHODS |
| | (AMMENDED 2001 FBC SECTION 103.7). |
| | PLEASE PROVIDE LETTER FROM THE ENGINEER |
| | OF THE DRYER MANUFACTURER APPROVING THE |
| | INSTALLATION OF THE BOOSTER FAN WITHOUT |
| | VOIDING THE WARRANTY OF THE DRYER. |
| | |