| 2005-10-17 00:00:00 | *** NOTE ADDED *** |
| | |
| | |
| | PLEASE KNOW, AS OF JAN 1ST, 2005, WE ARE |
| | NOW UNDER THE 2003 NFPA-101. |
| 2005-09-04 00:00:00 | *************************************** |
| | |
| | PLEASE BEAR IN MIND CODES CHANGES AS OF |
| | OCTOBER 1, 2005 WILL TAKE AFFECT. |
| | ONLY PROJECTS/BUILDING PERMITS SUBMITTED |
| | BEFORE SUCH DATE WILL FALL UNDER PRESENT |
| | CODE. |
| | THIS WILL NOT AFFECT ELECTRICAL CODE |
| | CHANGE, AS 2005 NEC IS NOT SCHEDULED FOR |
| | ADOPTION UNTIL OCT 1ST, 2006. |
| | |
| | *************************************** |
| | |
| | |
| | |
| | ********* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE PROJECT IS SUBMITTED |
| | AS CONDO'S YET ELECTRICALSERVICES |
| | PROVIDED IS SHOWN AS EACH WOULD BE A |
| | TOWNHOUSE (FEE SIMPLE). |
| | PLEASE SEE WATER SERVICE SHOWS |
| | MULTI-FAMILY BLDG. |
| | PLEASE KNOW, IF THESE AS MULTI-FAMILY |
| | CONDO BLDGS; ONE SERVICE FOR EACH BLDG |
| | IS PERMITTED,230.2,230.70MAINS WILL BE |
| | REQUIRED TO BE GROUPED PER 230.72. |
| | MCB'S SHOWN IN EACH GARAGE PANEL IS |
| | PERMITTED. |
| | PLEASE ADJUST SERVICE FOR BLDG. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | AIC RATINGS ARE SHOWN FOR EACH PANEL, |
| | BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW |
| | SERVICE). |
| | |
| | 3)NOTE: PLEASE CLARIFY LOCATION OF |
| | DISHWASHER RECEPT. APPEARS TO BE SHOWN |
| | BEHIND UNIT? THIS IS ONLY A NOTE: |
| | |
| | 4))NOTE: PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | PLEASE SEE PLANS REDLINED FOR SOME |
| | MISSING W/IN 2' OF THE END OF A COUNTER |
| | OR 4' SPACING. |
| | UNIT "A"/STANDARD 2FLR,,, |
| | |
| | 5)NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | PLEASE SEE THESE HAVE BEEN REDLINED AT |
| | LOCATIONS OF NOTES. |
| | UNIT "B",3RD FLR OPT 6 2'OF WALL, UNIT |
| | "A"2ND FLR, WALL APPEARS TO BE OVER 12'? |
| | PLEASE SEE A COUPLE OF OTHER LOCATIONS. |
| | |
| | 6)NOTE: PLEASE SEE LOCATION OF A |
| | RECESSED LT FIXTURE IN CLOSET |
| | WASHER/DRYER LOCATION. THESE LOCATIONS |
| | TYPICALLY CONTAIN SHELVING ABOVE THE |
| | WASHER/DRYER'S. PLEASE SEE 410.8 FOR MIN |
| | CLEARENCE FROM LT AND FIXTURE TYPES. |
| | (WALL MOUNT)? AS SHOWN IN OTHER CLOSETS? |
| | |
| | 7 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS NEEDS |
| | TO BE SHOWN ABOVE THE GEN. KT/RECEPT |
| | LOADS. THIS SHOULD BE ABOVE THE FIGURED |
| | 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 8)NOTE: PLEASE LIST ALL THE REQUIRD ARC |
| | FAULT PROECTED CIRCUITS AS REQUIRED PER |
| | 2002 210.12 |
| | PLEASE KNOW, SD'S ARE BEING SHOWN |
| | CIRCUITED TO KITCHEN LIGHTING CIRCUIT, |
| | THIS IS OK, HOWEVER PLEASE KNOW, THIS |
| | WOULD ALSO REQUIRE ARC FAULT PROTECTION |
| | FOR THIS ADDITIONAL CIRCUIT. |
| | THIS IS ONLY A NOTE: |
| | |
| | 9)NOTE: PLEEASE SEE NFPA-72 (2002) |
| | EDITION,11.8.3.5. |
| | PLEASE PLACE NOTE ON PLANS WHICH STATES |
| | LOCATIONS OF SD'S TO BE A MIN OF 3' FROM |
| | BATH(S) AND KITCHEN DOORS AND 20' FROM |
| | KITCHEN COOKING APPLIANCES. |
| | ** PLEASE SEE EXCEPTION TO 20' FROM |
| | COOKING WITH TYOE OF SD USED.** |
| | PLEASE SEE PLANS SHOWS A SD IN KITCHEN |
| | AREA AT THIS TIME. |
| | |
| | 10)NOTE: PLEASE SEE MECHANICAL NOTES |
| | PERTAINING TO "DRYER BOOSTER FANS". |
| | AS PER MECHANICAL THESE MAY NOT BE |
| | PERMITTED AND ANY COMMENT THEY MAY HAVE |
| | WILL DIRECTLY AFFECT ELECTRICAL PLANS. |
| | THIS IS A NOTE, AS IT IS NOT AN NEC |
| | ISSUE. |
| | PLEASE SEE ALL SYSTEMS DO HAVE BE |
| | LISTED.110.3,90.7 |
| | |
| | 11)NOTE: PLEASE SEE ARCHITECTS TITLE |
| | BLOCK SHALL ALSO CONTAIN THE PRINTED |
| | LICENSE NUMBER FOR ARCHITECT OF RECORD. |
| | FAC 61G1-16.004. |
| | PLEASE SEE THIS COMMENT IS FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | PLEASE KNOW THIS COMMENT DOES NOT APPLY |
| | TO KAMM CONSULTING'S TITLE BLOCK. |
| | |
| | PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLF/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | ** PLEASE SEE THIS MAY BE CONSIDERED A |
| | "THRESHOLD" PROJECT. IF SO, THREE SETS |
| | OF PLANS WILL BE REQUIRED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| 2005-09-03 00:00:00 | IN ELEC FOR REVIEW |
| | NOTES TO FOLLOW. |