Plan Review Notes For Permit 05081303
Permit Number 05081303
Review Stop B
Sequence Number 1
Notes
Date Text
2005-09-16 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED N.O.C.
  
 2- ENERGY CALCS ARE GETTING THE CEILING
 FAN CREDIT. REVISE ELECTRICAL PLAN TO
 INCLUDE CEILING FAN SIZE IN ALL ROOMS,
 INCLUDING THE CEILINGS FANS REQ'D IN THE
 GREAT ROOM. SEE TABLE 6-6 CHAPTER 13 FBC
  
  
 3- REVISE ROOF FRAMING PLAN @ ENTRY
 PORCH ROOF AREA. CONCRETE BEAM DOESN'T
 GO BACK TO THE FOYER AREA. ALSO, REVISE
 KNEEWALL ON THE RIGHT HAND SIDE. THERE
 IS NOT CONCRETE BEAM EITHER. REVISE AS
 REQUIRED AND SPECIFIY CORRESPONDING
 CONNECTOR. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 4- REVISE TRUSS ANCHOR SCHEDULE. REVISE
 NUMBER OF NAILS FOR HUS26. SEE CATALOGUE
  
 5- PROVIDE COMPLETE FLORIDA/LOCAL
 PRODUCT APPROVAL FOR:
 A) 1 HR ATRIUM DOOR. NEED INSWING DOOR
 TO MATCH PLANS.
 B) ROOF TILE.
 C) SINGLE HUNG WINDOWS.
 D) FIXED WINDOWS.
 E) WINDOW MULLION SPECIFIED AT GREAT
 ROOM FIXED WINDOWS.
  
 6- SPECIFY MULLION SIZE AND ANCHORS FOR
 FIXED WINDOWS AT GREAT ROOM. 1X MULLION
 DOESN'T RESIST THE DESIGN PRESSURES.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.