| 2005-08-19 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) FBC 1606.2.5THE SUBMITTED FLAT ROOF |
| | PRODUCT APPROVAL NOA IS MISSING PAGES. |
| | IT MUST INCLUDE THE PAGES THAT DESCRIBE |
| | THE PROPOSED ROOF SYSTEM AND STATE THE |
| | DESIGN WIND PRESSURE OF THAT SYSTEM. |
| | |
| | 2) THE PRODUCT APPROVAL SHEETS SHALL BE |
| | MARKED, AS APPROPRIATE, TO IDENTIFY |
| | WHICH SYSTEM IS TO BE USED. |
| | |
| | 3) NOTE: |
| | WHEN SELECTING A SYSTEM, PLEASE NOTE |
| | THAT IF 'GENERAL LIMITATION #9' IS CITED |
| | NEXT TO THE DESIGN WIND PRESSURE, THAT |
| | LIMITATION PROHIBITS RATIONAL ANALYSIS |
| | OR EXTRAPOLATION TO ENHANCE THE UPLIFT |
| | PRESSURE AT PERIMETER AND CORNER AREAS |
| | BY REDUCING THE FASTENER SPACING IN |
| | THESE AREAS.IN THAT CASE, EITHER |
| | SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT |
| | APPROVAL) THAT DOES NOT CITE GENERAL |
| | LIMITATION #9.ALTERNATIVELY IF THE |
| | SELECTED SYSTEM DOES CITE GENERAL |
| | LIMITATION #9, IT MUST HAVE A MAXIMUM |
| | DESIGN PRESSURE THAT EXCEEDS THE |
| | PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 |
| | PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR |
| | LESS). |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |