2005-08-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1606.2.5THE SUBMITTED FLAT ROOF
 PRODUCT APPROVAL NOA IS MISSING PAGES.
 IT MUST INCLUDE THE PAGES THAT DESCRIBE
 THE PROPOSED ROOF SYSTEM AND STATE THE
 DESIGN WIND PRESSURE OF THAT SYSTEM.
  
 2) THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH SYSTEM IS TO BE USED.
  
 3) NOTE:
 WHEN SELECTING A SYSTEM, PLEASE NOTE
 THAT IF 'GENERAL LIMITATION #9' IS CITED
 NEXT TO THE DESIGN WIND PRESSURE, THAT
 LIMITATION PROHIBITS RATIONAL ANALYSIS
 OR EXTRAPOLATION TO ENHANCE THE UPLIFT
 PRESSURE AT PERIMETER AND CORNER AREAS
 BY REDUCING THE FASTENER SPACING IN
 THESE AREAS.IN THAT CASE, EITHER
 SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT
 APPROVAL) THAT DOES NOT CITE GENERAL
 LIMITATION #9.ALTERNATIVELY IF THE
 SELECTED SYSTEM DOES CITE GENERAL
 LIMITATION #9, IT MUST HAVE A MAXIMUM
 DESIGN PRESSURE THAT EXCEEDS THE
 PRESSURE IN ROOF ZONE 3 (TYPICALLY -89
 PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR
 LESS).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO