| 2006-06-02 00:00:00 | ************ UNSAT ************** |
| | |
| | |
| | 1) NOTE: PLEASE SEE RISER IS NOW ON |
| | PLANS, HOWEVER IS SERVICE NEW OR |
| | EXISTING??? |
| | ON ONE SET OF PREVIOUS REVIEWED PLANS IT |
| | WAS STATED AS EXISTING AND AIC RATINGS |
| | ARE NOT REQUIRED, HOWEVER PREVIOUS PLANS |
| | HAVE ALSO SHOWN THE SERVICE AS NEW AND |
| | AIC RATINGS WERE REQUESTED. |
| | PLEASE INDICATE IF SERVICE IS NEW OR |
| | EXISTING? IF NEW PROVIDE AIC RATINGS |
| | FOR MAINS ETC. PER 110.9, 215.5 |
| | |
| | 2) NOTE: PLEASE SEE PLANS STILL DO NOT |
| | CONTAIN THE PANEL SCHEDULE FOR THE |
| | CABANA SHOWING THE CIRCUITS, OVERCURRENT |
| | PROTECTION FOR CIRCUITS AND WIRE SIZES?? |
| | THIS WAS SOMETHING WHICH WAS ON PREVIOUS |
| | PLANS, HOWEVER IS NOT ON THESE PLANS.?? |
| | PLEASE BE SURE THE REQUIRED DEDICATE AND |
| | ARC FAULT CIRCUITS ARE SHOWN. |
| | PLEASE SEE THE A/C SHEETS CONTAIN PANELS |
| | SCHEDULES FOR HOUSE AND CABANA, HOWEVER |
| | THESE PANELS SCHEDULES ARE "BLANK"?? |
| | 210.12,210.11C3, ETC. |
| | |
| | 3) NOTE: PLEASE INCLUDE THE OCP FOR THE |
| | NEW SUB PANEL FEED. THE RISER MENTIONS |
| | NEW 2-POLE, HOWEVER WHAT SIZE IS THIS?? |
| | |
| | 4) NOTE: PLEASE SEE IF THE SERVICE IS |
| | NEW, PLEASE PROVIDE A MIN OF TWO GRND |
| | RODS AND CWP AT MAIN HOUSE. IF THE |
| | SERVICE IS EXISTING, THEN THIS IS NOT |
| | NEEDED. |
| | 250.50 |
| | |
| | 5) NOTE: PLEASE SHOW THE LOCATION AND |
| | DISCONNECTING MEANS FOIR THE AHU AND CU. |
| | PLEASE SEE THE MECH SHEET SHOWS THE AHU |
| | IN CLOSET, HOWEVER THE ELECTRICAL PLANS |
| | ONLY INDICATE THE WATER HEATER.?? |
| | 440.11, 215.5 |
| | |
| | 6) NOTE: PLEASE SEE LOCATION OF NEW SUB |
| | PANEL IS NOT SHOWN ON PLANS?? |
| | |
| | |
| | 7) NOTE: PLEASE KNOW , IT IS THE |
| | RESPONSIBILITY OF THE ENGINEER SIGNING |
| | AND SEALING PLANS ONLY TO SIGN AND SEAL |
| | PLANS IN WHICH WERE DONE BY SAID |
| | ENGINEER OR IS UNDER HIS DIRECT |
| | SUPERVISION.FS 471 |
| | PLEASE KNOW, IT IS ALSO THE |
| | RESPONSIBILTY TO REVIEW AND CHECK PLANS |
| | FOR CODE COMPLIANCE BEFORE SIGNING AND |
| | SEALING SAID PLANS. |
| | THIS IS THE 7TH REVIEW FOR THIS SCOPE OF |
| | WORK. PLEASE KNOW IF ALL CORRECTIONS ARE |
| | NOT MADE FOR THE FOLLOWING REVIEW, A 4X |
| | FEE WILL BE ACCESSED PER FS 553.80(2)(B) |
| | AND ALL PLANS RETAINED FOR THIS JOB FROM |
| | PREVIOUS REVIEWS AND NEW PLANS WILL BE |
| | TURNED OVER TO THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS, AND LEGAL |
| | COUNSEL FOR REVIEW. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |