| Plan Review Notes For Permit 05081294 |
| Permit Number |
05081294 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-11-21 00:00:00 | *** UNSAT *** | | | | | | | | | ** PLEASE SEE ZONING COMMENT. THE | | | PROPOSED RESIDENCE IS NOT PERMITTED. | | | | | | | | | 1)NOTE: PLEASE SEE PLANS INDICATE | | | KITCHEN SM APPLIANCE CIRCUITS, WHICH IS | | | ALSO NOT PERMITTED BY ZONING. | | | | | | 2)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | AND EXISTING PANEL SCHEDULE. | | | PLEASE SEE FEEDERS, #3, #4. | | | PLEASE SEE MIN PER 310.15B6 | | | | | | 3)NOTE: PLEASE SEE MIN LOAD CALCULATIONS | | | PER 220.31B. | | | PLEASE REVISE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|