| 2005-12-15 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) THE INTERNAL PRESSURE COEIFFICIENT IS |
| | MISSING THE PLUS AND MINUS SIGNS |
| | INDICATING POSITIVE AND NEGATIVE |
| | PRESSURES. SEE ASCE 7-98. |
| | |
| | 4) AN EGRESS DOOR WITH A MINIMUM 32" |
| | WIDE CLEAR OPENING IS REQUIRED. IF USING |
| | A DOUBLE DOOR ONE OF THE LEAFS MUST |
| | COMPLY. SEE 2001 FBC 1003.2.3, 1012.1.7 |
| | AND 1012.1.8. |
| | |
| | 5) PROVIDE A SITE PLAN SPECIFING THE |
| | ASSUMED PROPERTY LINE BETWEEN THE THE |
| | TWO STRUCTURES LOCATED ON THE SAME LOT. |
| | PROVIDE CALCULATIONS OF THE PERCENT OF |
| | WALL AREA ALLOWED AS OPENINGS BY FBC |
| | TABLE 600 FOR THE EXISTING AND THE NEW |
| | STRUCTURES. SEE 2001 FBC 504 AND TABLE |
| | 600. (THIS HAS NOTHING TO DO WITH |
| | OPENING PROTECTIVES REQUIRED BY FBC 705 |
| | WHICH DOES NOT APPLY TO R3 OCCUPANCIES.) |
| | |
| | |
| | 6) ADDRESS COMMENTS OF OTHER REVIEWS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |