| 2005-09-23 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) THE INTERNAL PRESSURE COEIFFICIENT IS |
| | MISSING THE PLUS AND MINUS SIGNS |
| | INDICATING POSITIVE AND NEGATIVE |
| | PRESSURES. SEE ASCE 7-98. |
| | |
| | 4) AN EGRESS DOOR WITH A MINIMUM 32" |
| | WIDE CLEAR OPENING IS REQUIRED. IF USING |
| | A DOUBLE DOOR ONE OF THE LEAFS MUST |
| | COMPLY. SEE 2001 FBC 1003.2.3, 1012.1.7 |
| | AND 1012.1.8. |
| | |
| | 5) THE BEDROOM WINDOW MUST COMPLY WITH |
| | THE EMERGENCY EGRESS REQUIREMENTS OF |
| | 1005.4. |
| | |
| | 6) PROVIDE AN EXTERIOR WALL SECTION ON |
| | THE PLANS. FBC 104.2 |
| | |
| | 7) 1804.1.3 THE BOTTOM OF THE FOUNDA- |
| | TION SHALL EXTEND NO LESS THAN 12" |
| | BELOW FINISH GRADE. |
| | |
| | 8) SPECIFY A 1.5 INCH RECESS IN THE |
| | CONCRETE FLOOR SURFACE WHERE THE |
| | EXTERIOR WALL MASONRY UNITS BEAR. CITY |
| | AMENDMENTS TO FBC 2111.1.9. |
| | |
| | 9) CITY AMENDMENTS TO FBC 1804.1.7 |
| | REQUIRE THE FLOOR ELEVATION AT THE |
| | PERIMETER OF A MONOLITHIC FOUNDATION AT |
| | HABITABLE AREAS TO BE A MINIMUM OF 4 |
| | INCHES ABOVE THE EXTERIOR FINISH GRADE. |
| | |
| | 10)FL BLD CODE 2309.6 ATTIC ACCESS, |
| | PROVIDE ATTIC ACCESS 20"X36" MINIMUM. |
| | |
| | 11) SPECIFY ATTIC VENTILATION AS |
| | REQUIRED BY FBC 2309.7. |
| | |
| | 12) SPECIFY THE LOCATION OF THE 40 GAL. |
| | ELECTRIC WATER HEATER. FBC 104.2 |
| | |
| | 13) PROVIDE A SITE PLAN SPECIFING THE |
| | ASSUMED PROPERTY LINE BETWEEN THE THE |
| | TWO STRUCTURES LOCATED ON THE SAME LOT. |
| | PROVIDE CALCULATIONS OF THE PERCENT OF |
| | WALL AREA ALLOWED AS OPENINGS BY FBC |
| | TABLE 600 FOR THE EXISTING AND THE NEW |
| | STRUCTURES. FBC 504 AND TABLE 600. |
| | |
| | 14) SPECIFY THE CONNECTION TYPE AND THE |
| | ANCHOR TYPE THAT WILL BE USED FOR THE |
| | STORM PANELS. SEE SHEET 4 OF THE PRODUCT |
| | APPROVAL. THE STORM PANEL INSTALLATION |
| | SCHEDULE LISTS WING NUTS AS THE ANCHOR |
| | TYPE. THIS IS NOT ONE OF THE ANCHORS |
| | LISTED ON THE PRODUCT APPROVAL. THE |
| | SCHEDULE ALSO INDICATES THAT THE PANELS |
| | ARE BOLTED. THIS REFERS TO PANELS WITH |
| | LONG SPANS THAT ARE REQUIRED TO BE |
| | BOLTED TOGETHER IN THE MIDDLE OF THE |
| | SPAN. THIS IS NOT NECESSARY FOR YOUR |
| | PROJECT. |
| | |
| | 15) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SUBMIT A |
| | COVER SHEET FOR THE ROOF SHINGLES. |
| | |
| | 16) THE FL COVER SHEET FOR THE STANLEY |
| | DOOR SYSTEM DOES NOT MATCH THE MIAMI |
| | DADE NOA. |
| | |
| | 17) THE MIAMI DADE NOA FOR THE SINGLE |
| | HUNG WINDOWS IS NOT THE ONE LISTED ON |
| | THE STATE WEBSITE FOR THE FL # |
| | SUBMITTED. THE CORRECT ONE IS NOA # |
| | 02-1203.02. |
| | |
| | 18) THE DRAWINGS ATTACHED TO THE STANLEY |
| | DOOR NOA DO NOT BELONG WITH THE NOA. |
| | THEY HAVE DIFFERENT APPROVAL NUMBERS. |
| | |
| | 19) SUBMIT PRODUCT APPROVALS FOR THE |
| | SINGLE INSWING EXTERIOR DOOR AND THE |
| | DOUBLE OUTSWING EXTERIOR DOOR. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |
| | |
| | |