Plan Review Notes
Plan Review Notes For Permit 05081269
Permit Number 05081269
Review Stop M
Sequence Number 1
Notes
Date Text
2005-08-23 00:00:00***DENIED***
 1) FLOOR PLAN NOT ADEQUATE
 2) ALL ROOMS NEED TO BE DESIGNATED
 3) NEED TOTAL SQUARE FEET UNDER AIR
 4) NEED A/C EQUIPMENT INFORMATION.
 5) NEED SIZS OF DUCTS, AND GRILLLS WITH
 CFM'S SHOWING.
 6) SHOW IF GRILLS ARE SUPPLY OR RETURN.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON #805-6729 OR PATTY KRAUSS
 #805-6719.