2006-02-28 00:00:00********** UNSAT 2ND REVIEW ********
  
 ** PLEASE SOME NOTES FROM PERVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM THE PREVIOUS REVIEW WITH
 ADDED NOTING FOR CLARIFICATION.
 PLEASE SEE NEW NOTES FOR DESIGNERS.
  
  
 1)NOTE: NOTE #1 NO, PLEASE SHOW ALL
 CIRCUITING, SOME NEW CIRCUITS ARE SHOWN
 , HOWEVER THERE ARE STILL SOME MISSING.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE LOCAL
 BRANCH CIRCUIT LIGHTING SHALL ALSO FEED
 THE EM / EXT LTS IN THAT AREA.
  
 ** PLEASE SHOW NEW CIRCUITING ON PLANS
 AND CORRELATE WITH EXISTING PANEL
 SCHEDULE TO BE SUBMITTED.
 215.5
  
 2)NOTE: NOTE #2, NO, PLEASE SEE THE LOAD
 CALCULATIONS FROM PREVIOOUS PLANS WERE
 REMOVED FROM NEW SHEETS AND ONLY
 CONNECTED LOADS? ARE SHOWN. PLEASE KNOW,
 EVEN SHOWING SOME OF THESE LOADS AS
 CONNECTED LOADS, STILL DO NOT CORRELATE
 WITH THE MIN LOADS REQUIRED PER NEC.
 PLEASE SEE 220.3,220.10,220.13, ETC AND
 CONTINUOUS LOADS PER 215.3,230.42 ETC.
  
 ** PLEASE SEE NEC 220.13 FOR KNOWN
 RECEPT LOADS FOR LOAD CALCS.
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%, 215.3,230.42 ETC.
 PLEASE SEE ANY DEDICATED RECEPT LAODS
 MAY BE OF A HIGHER VALUE.
  
 3)NOTE: NOTE #3 OK, PLANS INDICATE THE
 DOOR BEING LOCATED INSIDE FOR THE
 ELEVATION AS SHOWN?
 RESPONSE LTR MENTIOSN THE REVISED
 DETAIL.
  
 ** PLEASE CORRELATE SEC AA FOR
 ELEVATION AND FLR PLANS. PLEASE SEE BLDG
 REVIEW COMMENTS AS ONE SHOWS A NEW
 FRENCH DOOR AND THE OTHER SHOWS A
 WINDOW?
 IF THERE WILL BE AN EGRESS DOOR, PLEASE
 INCLUDE ANY ELECTRICAL REQUIRED.
 (EXIT, LT)?
  
 4)NOTE: PLEASE SEE MISSING CERTIFICATE
 OF AUTHORIZATION FOR ENGINEERING FIRM AS
 SHOWN ON PLANS. PLEASE SEE FAC
 61G15-23.002, FS 471.023.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS CONTAINING THE TITLE BLOCK
 FOR SAID ENGINEERING FIRM.
  
 5)NOTE: PLEASE SEE "SEALS RULE" FROM THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 WHICH PER RULING DATE FEB 5, 2004 ,
 61G15-23.001REQUIRED ALL SEALS WITH
 THE WORDING OF "CERTIFICATE" TO BE
 CHANGED TO THE USE OF "LICENSE" IN SAID
 SEAL. PLEASE KNOW, AN EXTENSION WAS
 GIVEN TO THE DATE OF DEC 31ST, 2005.
 PLEASE KNOW AS OF JAN 1ST, 2006 ALL
 SEALS SHALL ONLY CONTAIN THE WORDING OF
 "LICENSE". PLEASE ADJUST ACCORDINGLY.
  
 6)NOTE: PLEASE SEEA NOTICE IS GIVEN AT
 THIS TIME WITH RESPECT TO THE DESIGN
 PROFESSIONAL(S) TO FS 553.80(2)(B) AND
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
 PLEASE BE SURE TO ADDRESS ALL COMMETS.
  
  
 **PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  