| 2006-02-28 00:00:00 | ********** UNSAT 2ND REVIEW ******** |
| | |
| | ** PLEASE SOME NOTES FROM PERVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM THE PREVIOUS REVIEW WITH |
| | ADDED NOTING FOR CLARIFICATION. |
| | PLEASE SEE NEW NOTES FOR DESIGNERS. |
| | |
| | |
| | 1)NOTE: NOTE #1 NO, PLEASE SHOW ALL |
| | CIRCUITING, SOME NEW CIRCUITS ARE SHOWN |
| | , HOWEVER THERE ARE STILL SOME MISSING. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF EM/ |
| | EXT LTS. |
| | THE BRANCH CIRCUIT FEEDING THE LOCAL |
| | BRANCH CIRCUIT LIGHTING SHALL ALSO FEED |
| | THE EM / EXT LTS IN THAT AREA. |
| | |
| | ** PLEASE SHOW NEW CIRCUITING ON PLANS |
| | AND CORRELATE WITH EXISTING PANEL |
| | SCHEDULE TO BE SUBMITTED. |
| | 215.5 |
| | |
| | 2)NOTE: NOTE #2, NO, PLEASE SEE THE LOAD |
| | CALCULATIONS FROM PREVIOOUS PLANS WERE |
| | REMOVED FROM NEW SHEETS AND ONLY |
| | CONNECTED LOADS? ARE SHOWN. PLEASE KNOW, |
| | EVEN SHOWING SOME OF THESE LOADS AS |
| | CONNECTED LOADS, STILL DO NOT CORRELATE |
| | WITH THE MIN LOADS REQUIRED PER NEC. |
| | PLEASE SEE 220.3,220.10,220.13, ETC AND |
| | CONTINUOUS LOADS PER 215.3,230.42 ETC. |
| | |
| | ** PLEASE SEE NEC 220.13 FOR KNOWN |
| | RECEPT LOADS FOR LOAD CALCS. |
| | PLEASE SHOW ALL CONTINUOUS LOADS AT |
| | 125%, 215.3,230.42 ETC. |
| | PLEASE SEE ANY DEDICATED RECEPT LAODS |
| | MAY BE OF A HIGHER VALUE. |
| | |
| | 3)NOTE: NOTE #3 OK, PLANS INDICATE THE |
| | DOOR BEING LOCATED INSIDE FOR THE |
| | ELEVATION AS SHOWN? |
| | RESPONSE LTR MENTIOSN THE REVISED |
| | DETAIL. |
| | |
| | ** PLEASE CORRELATE SEC AA FOR |
| | ELEVATION AND FLR PLANS. PLEASE SEE BLDG |
| | REVIEW COMMENTS AS ONE SHOWS A NEW |
| | FRENCH DOOR AND THE OTHER SHOWS A |
| | WINDOW? |
| | IF THERE WILL BE AN EGRESS DOOR, PLEASE |
| | INCLUDE ANY ELECTRICAL REQUIRED. |
| | (EXIT, LT)? |
| | |
| | 4)NOTE: PLEASE SEE MISSING CERTIFICATE |
| | OF AUTHORIZATION FOR ENGINEERING FIRM AS |
| | SHOWN ON PLANS. PLEASE SEE FAC |
| | 61G15-23.002, FS 471.023. |
| | THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL SHEETS CONTAINING THE TITLE BLOCK |
| | FOR SAID ENGINEERING FIRM. |
| | |
| | 5)NOTE: PLEASE SEE "SEALS RULE" FROM THE |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS |
| | WHICH PER RULING DATE FEB 5, 2004 , |
| | 61G15-23.001REQUIRED ALL SEALS WITH |
| | THE WORDING OF "CERTIFICATE" TO BE |
| | CHANGED TO THE USE OF "LICENSE" IN SAID |
| | SEAL. PLEASE KNOW, AN EXTENSION WAS |
| | GIVEN TO THE DATE OF DEC 31ST, 2005. |
| | PLEASE KNOW AS OF JAN 1ST, 2006 ALL |
| | SEALS SHALL ONLY CONTAIN THE WORDING OF |
| | "LICENSE". PLEASE ADJUST ACCORDINGLY. |
| | |
| | 6)NOTE: PLEASE SEEA NOTICE IS GIVEN AT |
| | THIS TIME WITH RESPECT TO THE DESIGN |
| | PROFESSIONAL(S) TO FS 553.80(2)(B) AND |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | PLEASE BE SURE TO ADDRESS ALL COMMETS. |
| | |
| | |
| | **PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |