Plan Review Notes
Plan Review Notes For Permit 05081227
Permit Number 05081227
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-19 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASE SHOW GROUNDING ATTACHMENT
 AT SECONDARY SIDE OF TRANSFORMER FOR THE
 SEPRATELY DERIVED SYSTE.
 250.30,250.24, 250.122, 250.6 SIZING OF
 GROUNDING SHALL BE PER 250.66
  
 2)NOTE: PLEASE PROVIDE INFORMATION FOR
 LOAD OF NEW CHILLER.
 PLEASE CLARIFY IF LOAD IS THE SAME AS
 PREVIOUS OR IF THERE IS ANY LOAD
 INCREASE. 215.5,220
 PLEASE BE SURE LARGEST MOTOR IS 125%.
 215.3,230.42 ETC.
  
 3)NOTE: PLEASE INCLUDED NEW PROPOSED LOW
 VOLTAGE WORK BEING DONE.
  
 4)NOTE: PLEASE SEE 300.19(A) FOR
 POSSIBLE "PULL-BOXES" AND VERTICAL
 SUPPORTS REQUIRED FOR CONDUCTORS.
  
 5)NOTE: PLEASE SHOW ANY EXISITNG AS
 EXISITNG. IT IS THIS OFFICES
 UNDERSTANDING THE CONDUCTORS, AND SOME
 DISCONNECTS ARE EXISTING, HOWEVER PLANS
 INDICATE THESE AS NEW?
  
 6)NOTE: PLEASE SHOW THE LOCATION OF THE
 NEW TRANSFORMER IN BLDG. PLEASE SEE
 450.13, 450.9,450.21 ETC FOR MIN RATINGS
 OF ROOM, CLEARENCES ETC.
  
 7)NOTE: PLEASE BE SURE PLANS ARE SIGNED
 BY THE ENGINEER OF RECORD AS ON FILE.
 PLEASE SEE FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  