| Date |
Text |
| 2005-09-10 00:00:00 | ******** UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE RISER DIAGRAM NEEDS |
| | TO BE COMPLETELYREVISED TO MEET ZONING |
| | GREEN CARD. |
| | THIS MAY ONLY BE A MAIN HOUSE W/ A |
| | GARAGE APT. THIS WOULD ONLY BE ALLOWED |
| | TO HAVE TWO METERS. ONE FOR EACH AND NO |
| | HOUSE PANEL. |
| | |
| | PLEASE SEE ANY LEGAL CONVERSIONS, MUST |
| | BE RESERCHED TO ALLOW FOR ANY MORE THAN |
| | THE TWO ON GREEN CARDS AS INDICATED. |
| | ALL RESERCH REQUESTS MUST GO THROUGH |
| | APRIL PICCIRILLO, 805-6658 |
| | |
| | |
| | |
| | 2)NOTE: PLEASE SEE RISER SUBMITTED IF |
| | APPROVED BY ZONING HAS CORRECTION |
| | NEEDED. |
| | PLEASE SEE ALL FEEDS FOR EACH COME FROM |
| | LEFT SIDE OF METER CENTER. |
| | PLEASE LABEL ALL MAINS ON METER CENTER |
| | FOR EACH HOUSE/APT. |
| | PLEASE SEE TWO APT "B"'S ARE SHOWN. |
| | PLEASE SEE MAIN HOUSE IS ALSO INDICATED |
| | AS APT "B".?? |
| | |
| | |
| | 3)NOTE: PLEASE SEE ALL CONTINUOUS LOADS |
| | ARE TO BE SHOWN AT 125%. |
| | HEAT PUMP, POOL PUMP ETC. |
| | 215.3,230.42,680.9 |
| | |
| | 4)NOTE: PLEASE SEE MIN BRANCH CIRCUIT |
| | CONDUCTOR AMPACITY FOR TANKLESS WATER |
| | HEATER UNITS MUST BE 125%. |
| | 422.13 |
| | PLEASE ALSO SEE 422.11F1 |
| | |
| | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 6)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 |
| | |
| | 7 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC 210.12 |
| | |
| | 8)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 9) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | MUST BE 20A AND #12. |
| | |
| | 10) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | ALSO 210.8 FOR GFI. |
| | |
| | 11)NOTE: PLEASE SEE MISSING RECEPT |
| | REQ'D FOR A/C EQUIPMENT. 210.63 |
| | |
| | 12)NOTE: PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | SEE REDLINED PLANS FOR MISSING. |
| | |
| | 13)NOTE: PLEASE SEE SEE SPA TUB SHOWN, |
| | HOWEVER NO ELECTRICAL GFI ETC?? |
| | 680.71 |
| | IS THIS AN ELECTRICAL JACUZZI TUB? |
| | |
| | 14)NOTE: PLEASE SEE FBC CHAPTER 34 WITH |
| | RENOVATIONS TO EXSITNG DWELLINGS. |
| | PLEASE SEE ALL MUST BE BROUGHT UP TO |
| | CODE, INCLUDING 2NF FLR AT DEATCHED |
| | BLDG. |
| | PLEASE PROVIDE COMPLETE LAYOUT FOR |
| | EITHER EXSITNG TO MEET CODE OR NEW TO BE |
| | DONE ON SCOPE OF WORK. |
| | |
| | 15)NOTE: PLEASE SEE ADMINISTRATIVE |
| | AMENDMENTS, 104.6.5, WHICH REQUIRES ALL |
| | LABOR AND MATERIALS TO BE INCLUDED IN |
| | VALUE OF PERMIT APPLICATION. |
| | PLEASE SEE VALUE FOR SERVICE CHANGE |
| | PERMIT WILL ALSO BE REQUIRED TO BE |
| | UPGRADED. |
| | IFVALUES ARE NOT AJUSTED, A VALUATION |
| | WILL BE GIVEN BASED ON TABLE IN "MARSHAL |
| | SWIFT " GUIDES ADOPTED UNDER FBC. |
| | |
| | ** PLEASE SEE MANY OF THE ABOVE COMMENTS |
| | DEPEND ON ZONING AND APPROVAL FOR MORE |
| | THAN TWO METERS AND DETACHED BLDG |
| | POSSIBLY REMAINING GARAGE WITH APT |
| | ABOVE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |