| Date |
Text |
| 2005-10-05 00:00:00 | *** REDLINED PLANS. | | | | | | CONDUCTORS FROM ATS TO MCB PANELS TO BE | | | MAIN OF 1/0'S, #3' SHOWN. | | | NO EQUIPMENT GROUNDING CONDUCTOR FROM | | | METER TO ATS/ FIRST MEANS OF DISCONNECT. | | | 250.6,250.24 |
|