| 2005-09-08 00:00:00 | *** DENIED *** | | | 1) PLANS MUST INICATE ANY BUILDING | | | OPENINGS (WINDOWS, DOORS, ROOF/EAVE | | | VENTS.GENERATOR EXHAUST MUST BE TEN | | | FEET AWAY FROM ANY BUILDING OPENINGS, | | | AND TEN FEET AWAY FROM ADJACENT | | | BUILDING OPENINGS. 2001 FBC/M 804.3.3 | | | 2) NATURAL GAS PIPING WILL REQUIRE A | | | GAS PERMIT APPLICATION BY A LICENSE | | | PLUMBING CONTRACTOR. | | | 3) PLEASE SEE ELECTRICAL REVIEW NOTES | | | #1 AND "#7" . | | | IF YOU HAVE ANY QUESEIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719 . |
|