| 2005-09-01 00:00:00 | ********* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE COMMENTS FROM OTHER |
| | REVIEWER(S). BLDG FOR SLAB DETAIL |
| | SUBMITTED. |
| | |
| | 2)NOTE: PLEASE SEE SITE PLAN SUBMITTED |
| | SHOWS GENERATOR RIGHT NEXT TO HOUSE?? |
| | PLEASE SHOW SET BACK AND DIMENTIONS FROM |
| | DWELLING STRUCTURE. |
| | PLEASE SEE MECH NOTES, MUST BE 10' FROM |
| | ANY OPENINGS TO HOUSE,ATTIC VENTILATION, |
| | DOORS AND WINDOWS. |
| | |
| | 3)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | WITH PANEL SCHEDULES SUBMITTED. |
| | PLEASE SEE RISER SHOWS 2 PANELS, BOTH |
| | 200A WITH 2/0'S. PLEASE SEE PANEL "A" |
| | SHOWN AS 150A W/ #1 AS FEEDERS?? |
| | PLEASE SEE PANEL "C" IS NOT SHOWN ON |
| | RISER AND SEE PANEL "B" SHOWS 100A OCP |
| | ON #6 AWG. PLEASE SEE 240.4,310.16 ETC. |
| | |
| | 4)NOTE: PLEASE SEE EQUIPMENT GROUNDING |
| | CONDUCTOR SHOWN FROM METER TO FIRST |
| | MEANS OF DISCONNECT. |
| | PLEASE SEE 250.6, |
| | |
| | 5)NOTE: PLEASE SEE EXISTING SERVICE IS |
| | SHOWN AS 400A, YET NEW MAIN AND ATS |
| | SHOWN BRINGS SERVICE DOWN TO 300A'S?? |
| | PLEASE SUBMIT MORE INFORMATION ON NEW |
| | MAIN SHOWN ON RISER. OCP? ETC |
| | AIC RATINGS FOR ALL EQUIPMENT BEING |
| | INSTALLED, MAIN, ATS ETC |
| | 702.6,110.9 ETC. |
| | |
| | 6)NOTE: PLEASE SUBMIT SPEC ON ATS, |
| | SHEETS SUBMITTED DOES NOT PROVIDE |
| | INFORMATION FOR RATING PER 225.36, |
| | 230.70 |
| | MUST INDICATE BEING RATED AS SERVICE |
| | EQUIPMENT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |