| Plan Review Notes For Permit 05081143 |
| Permit Number |
05081143 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-16 00:00:00 | 1) THE DRAWINGS FOR THE FOOTING DETAIL | | | NEEDS TO BE SIGNED/DATED AND SEAL BY THE | | | ENGINEER OF RECORD. | | | F.A.C. 61G15-23.002. | | | | | | 2) THE DRAWINGS FOR THE FOOTING DETAIL | | | HAS BEEN COPY AND PASTE ON THE NEW | | | SHEETS SUBMITTED.HOWEVER, THESE DRAWINGS | | | NEEDS THE PRINTED NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DRAWINGS. | | | | | | 3) THE FOOTING DETAIL STATES A MINIMUM | | | PSI OF 2500. THE CONCRETE DETAIL ON THE | | | ENGINEERED DRAWINGS STATES 3000 PSI. | | | PLEASE CLARIFY THESE TWO DETAILS. | | | | | | BUILDING PLAN REVIEW | | | MYRON JACOBS | | | TEL: (561)805-6726 | | | FAX: (561)659-8026 | | | |
|