| Plan Review Notes For Permit 05081141 |
| Permit Number |
05081141 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-23 00:00:00 | **** UNSAT **** | | | | | | 1)NOTE: PLEASE INCLUDE CIRCUITS TO | | | EXISTING PANELS. DEDICATED? ETC. | | | PLEASE ALSO SHOW ALL RECEPTS W/IN 6'S OF | | | WET BARS AS GFI/GFI PROTECTED. | | | 210.8A7 | | | | | | 2)NOTE: PLEASE SEE FBC 104.2.1, WHICH | | | REQUIRES THE PRINTED NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR PLANS AND | | | DESIGN. | | | | | | PLEASE SEE ANY COMMENTS FROM OTHER | | | TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFROMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|