| Plan Review Notes For Permit 05081141 |
| Permit Number |
05081141 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-22 00:00:00 | DENIED | | | | | | 1) THE INTERIOR NON-LOAD BEARING WALL | | | DETAIL ON SHEET ONE IS INCORRECT. FBC | | | 609.2.1 TYPE I AND TYPE II CONSTRUCTION. | | | PARTITIONS SHALL BE CONSTRUCTED OF | | | NONCOMBUSTIBLE MATERIALS. | | | | | | 2) ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN PER | | | CITY AMENDMENTS TO FBC 104.2.1. | | | | | | 3) THE CONTRACTOR IS A CBC AND IS | | | LIMITED TO WORK THAT WILL NOT AFFECT THE | | | STRUCTURAL MEMBERS OF THE BUILDING. | | | FS 489.105 | | | | | | 4) FBC 707.1 COMBUSTIBLES SHALL NOT BE | | | PERMITTED IN CONCEALED SPACES OF TYPES | | | I, II, OR IV CONSTRUCTION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|