| Plan Review Notes For Permit 05081135 |
| Permit Number |
05081135 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-09 00:00:00 | ******DENIED****** | | | | | | 1) PLANS SHOW ONE SET OF DOORS 1 HOUR | | | RATED AND THE OTHER DOOR FROM CORRIDOR | | | TO SUITE ISN'T? PLEASE EXPLAIN. | | | | | | 2) PLEASE SHOW LOCATIONS OF REQUIRED | | | FIRE EXTINGUISHERS THAT SHALL BE MOUNTED | | | TO SATISFY 75' TRAVEL DISTANCE | | | REQUIREMENT. | | | | | | 3) PLEASE PROVIDE FLAME SPREAD | | | INFORMATION FOR PROPOSED WALL SURFACE | | | FABRIC SYSTEM. | | | | | | 4) IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS, NEW DUCT SMOKE DETECTORS | | | SHALL BE WIRED TO CAUSE A GENERAL FIRE | | | ALARM CONDITION WHEN ACTIVATED. | | | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|