| Date |
Text |
| 2006-03-16 00:00:00 | ********** UNSAT ************** |
| | |
| | |
| | 1)NOTE: PLEASE SEE IT IS BEING NOTED BY |
| | OUR FEILD INSPECTORS THAT THE ADDRESS |
| | FOR THIS SCOPE OF WORK IS INCORRECT. |
| | PLEASE SEE PERMIT APPLICATION AND PCN |
| | ORIGINAL SET FORTH ON PERMIT APPLICATION |
| | SUBMITTED WAS FOR 1300 N FLAGLER DR. |
| | PLEASE VERIFY IF THIS WORK IS AT THIS |
| | ADDRESS. |
| | PLEASE ALSO INCLUDE JOBSITE ADDRESS ON |
| | PLANS AS REQUIRED PER FAC 61G15-23.002 |
| | |
| | 2)NOTE: PLEASE SEE PREVIOUS ELECTRICAL |
| | REVIEW WAS PASSEDON THE CONDITION THAT |
| | THE CORRECT VALUATION FOR SCOPE OF WORK |
| | BE INCREASED FOR ALL LABOR AND MATERIALS |
| | BEFORE ISSUING OF PERMIT BY THE |
| | CONTRACTOR. THIS WAS NOT DONE. |
| | PLEASE SEE FBC 104.6.5 AS ADOPTED CITY |
| | WIDE ADMINISTRATIVE CODE. |
| | THIS NOTE WAS TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW. |
| | |
| | **VALUE FOR SCOPE OF WORK TO INCLUDE ALL |
| | LABOR, EQUIPMENT AND MATERIALS, EVEN IF |
| | EQUIPMENT IS OWNER SUPPLIED. |
| | FBC 104.6.5 ADMINISTRATIVE AMENDMENTS. |
| | |
| | 3)NOTE: PLEASE SEE PLANS MUST BE |
| | RE-SEALED AS THE SEAL AS SHOWN IS NO |
| | LONGER ACCEPTABLE AS PUBLIC RECORD FOR |
| | THE FLORIDA BOARD OF PROFESSINAL |
| | ENGINEER'S. PLEASE SEE FAC 61G15-23.001 |
| | WHICH IN FEB 04 CHANGED TO NOW REQUIRE |
| | ALL SEALS TO CONTAIN THE WORDING OF |
| | "LICENSE" AND COULD NO LONGER USE |
| | "CERTIFICATE". PLEASE KNOW, AN EXTENSION |
| | WAS GRANTED TO THE DATE OF 12/31/05 TO |
| | GIVE ALL ENGINEERS 2 YRS TO OBTAIN NEW |
| | SEALS. WE CAN NO LONGER ACCEPT OLD |
| | SEALS. |
| | |
| | PLEASE UP VALUE, AND PLEASE SUBMIT |
| | REVISED CORRECTED SHEETS FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS, PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE KNOW, PERMIT MAY BE REVOKED IF |
| | FIRST TWO COMMENTS ARE NOT ADDRESSED IN |
| | A TIMELY FASHION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |