| 2005-09-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1. SHT P5.1 INDICATES THE REMOVAL OF THE |
| | DRINKING FOUNTAIN. MINIMUM FACILITIES |
| | REQUIRE DRINKING FOUNTAINS FOR THIS |
| | OCCUPANCY PER TABLE 403.1. PLEASE SHOW |
| | THE SQUARE FOOTAGE OF THE BUILDING AND |
| | INDICATE THE NUMBER OF DRINKING |
| | FOUNTAINS EXISTING IN THE BUILDING TO |
| | SHOW COMPLIANCE WITH MINIMUM FIXTURE |
| | FACILITIES. |
| | 2. PER SECTION 104.3.1.1 A SANITARY AND |
| | A WATER RISER DIAGRAM ARE REQUIRED FOR |
| | PLAN REVIEW. |
| | 3. INDIRECT WASTE SHALL DRAIN TO A FLOOR |
| | SINK OR A HUB DRAIN PER SECTIONS 802.3 |
| | AND 802.3.2. FLOOR DRAINS ARE NOT |
| | APPROVED FOR INDIRECT WASTE. |
| | 4. ALL DEVICES, APPURTENANCES, |
| | APPLIANCES AND APPARATUS INTENDED TO |
| | SERVE SOME SPECIAL FUNCTION, SUCH AS |
| | STERILIZATION, DISTILLATION, PROCESSING, |
| | COOLING, OR STORAGE OF ICE OR FOODS AND |
| | THAT CONNECT TO THE WATER SUPPLY SYSTEM, |
| | SHALL BE PROVIDED WITH PROTECTION |
| | AGAINST BACKFLOW AND CONTAMINATION OF |
| | THE WATER SUPPLY SYSTEM. SECTION 608.3. |
| | SHT P5.1 INDICATES WATER TO THE SHIELD |
| | COOLER AND TO THE HUMIDIFIER. INDICATE |
| | METHOD OF BACKFLOW PROTECTION. |
| | |