2006-07-15 00:00:00REDLINED ****
  
 1) PLACED ADDRESS OF 3810 ON MANY SHEETS
 AS SOME MOST STILL INDICATED 3802 AND
 SOME DI NOT INDICATE ADDRESS.
  
  
 2) AIC RATINGS OF MAINS SHALL BE 22,000
 MIN PER FAULT CURRENT CALCULATIONS ON
 PLANS.