2006-05-09 00:00:00*** DENIED ***
 1) ENERGY CAL'S ARE CALLING FOR 8 KW
 HEAT AND THE MECHANICAL PLANS ARE
 CALLING FOR 10 KW HEAT, THE TWO MUST
 COINCIDE PLEASE CORRECT.
  
 2) SHOW ALL SUPPLY AIR GRILL SIZES AND
 CFM'S ON MECHANICAL PLANS.
  
 3) SHOW A/C SUPPLY AIR DUCTS AND SIZES
 TO BATHROOMS.
  
 4) SHOW LOCATION OF A/C CONDENSER UNIT
 ON MECHANICAL PLANS.
  
 5) SHOW CONDENSATE DRAIN LINE ON
 MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  